| 2015-07-22 16:42:26 | 7/22/2015 |
| | PROJECT: PHILLIPS POINT #1100 |
| | PERMIT#: 15061450 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | 2) QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. WPB AMENDMENTS TO FBC 107.2.1.4 |
| | |
| | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC, WPB |
| | AMENDMENTS 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |