2015-07-02 17:37:39ROOF RECOVER, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE: PERMIT APPLICATION WAS SUBMITTED ON 6/30/15. THE
 NEW CODE TOOK EFFECT ON 6/30/15. THE CURRENT CODE IS
 FBC 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR THE RECOVERY SYSTEM TO BE INSTALLED. NOTE:
 COORDINATE WITH ITEM #3(D) BELOW.
  
 2- PROVIDE COPY OF THE TESTING REQUIRED BY LIMITATION
 #5.9 OF THE PRODUCT APPROVAL FL10264 REFERENCED BY THE
 CBUCK ENGINEERING REPORT SUBMITTED FOR THE RECOVERY
 ASSEMBLY.
  
 3- REVISE THE CBUCK ENGINEERING REPORT SUBMITTED:
 A) THE CURRENT CODE IS THE FBC-5TH EDITION (2014) NOT
 FBC-2010.
  
 B) THE MEAN ROOF HEIGHT IS INCORRECT. AND, THERE ARE
 SEPARATE FLAT ROOFS IN THIS BUILDING. PROVIDE SKETCH
 SHOWING ALL ROOFS AND MEAN ROOF HEIGHTS.
  
 C) NOT ALL THE FLAT ROOF S IN THIS BUILDING HAVE A
 3'-0" HIGH PARAPET. PROVIDE SKETCH SHOWING ALL THE FLAT
 ROOFS THAT ARE INVOLVED IN THIS PERMIT AND . REVISE
 CALCULATIONS AS REQUIRED. SEC. 1609 OF FBC-5TH EDITION.
  
 D) CURRENT ROOF COVERING FLORIDA PRODUCT APPROVAL IS
 FL10264-R12 NOT FL10264-R11. REVISE AS REQUIRED. DCA
 RULE 9N-3.
  
 E) ENGINEER TO REVISE THE ROOF SYSTEM ENGINEERING DATA
 ON PAGE 3 OF REPORT. THE CONSTRUCTION TYPE IS NOT NEW
 OR REROOF. THE PROPOSED INSTALLATION IS A RECOVER
 ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: ANY ROOFING EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMITS
  