2015-07-01 07:33:381ST REVIEW: FBC 2014 MECHANICAL
  
 1) ACCORDING TO WEST PALM BEACH PLANNING AND ZONING
 RECORDS, THE TWO STORY GUEST HOUSE WAS ORIGINALLY BUILT
 AS A GARAGE/APARTMENT. I HAVE NOT BEEN ABLE TO FIND A
 PERMIT IN THE PUBLIC RECORDS FOR THE CHANGE IN
 OCCUPANCY OF GARAGE TO GUEST HOUSE. PLEASE CLARIFY IF
 THIS PERMIT APPLICATION IS A SUB-PERMIT OF A MASTER
 PERMIT FOR THE GARAGE CONVERSION, OR IF SUBMITTAL OF A
 PERMIT APPLICATION AND PLANS ARE PENDING.
 2) IN REGARD TO THE PROPOSED AC SYSTEM, PREVIOUSLY
 UNCONDITIONED BUILDINGS NOW BEING CONDITIONED SHALL BE
 IN COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION CODE
 2014. PLEASE SEE SECTIONS R101.4.3, R101.4.8, AND
 R101.5. IN ACCORDANCE WITH SECTION R101.5.1.1 PLEASE
 SUBMIT TWO COPIES OF EITHER FORM R402, R405, OR A
 FLORIDA RESCHECK COMPUTER PRINTOUT TO DEMONSTRATE
 COMPLIANCE.
 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD AND TIE-DOWN ENGINEERING FOR MOUNTING THE
 CONDENSER.
 4) PROVIDE AN ELECTRICAL PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  