| Plan Review Notes For Permit 15061437 |
| Permit Number |
15061437 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2016-01-25 13:00:14 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE SIZE OF HEATING/COOLING UNIT FOR NEW BEDROOM: | | | SIZE OF HEATING AND COOLING WALL UNIT SHOWN ON PLANS IS | | | OVERSIZED FOR THE NEW BEDROOM. 8,000 BTU UNIT IS | | | OVERSIZED FOR A ROOM WITH LESS THAN 100S.F . PROVIDE | | | EQUIPMENT SIZING CALCULATIONS. SEC. C403.2.1 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). EQUIPMENT | | | CAN NOT EXCEED THE CALCULATED LOADS. SEC. C403.2.2 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
|