| 2015-12-16 11:07:58 | RESIDENTIAL (R2) ALTERATION, THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER OF RECORD WILL BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) |
| | IF PLANS ARE REJECTED ONE MORE TIME. |
| | |
| | 1- PLANS WERE REVISED AND NEW CASEMENT WINDOW WAS |
| | SPECIFIED ON PLANS FOR THE NEW BEDROOM. THE WINDOW NOW |
| | COMPLIES WITH EGRESS. NOW NEED TO PROVIDE PRODUCT |
| | APPROVAL (2 COPIES) FOR THE CASEMENT WINDOW AS REQUIRED |
| | BY FAC 61G20-3.002(3). |
| | |
| | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW TENANT SEPARATION WALL THAT MATCHES PROPOSED FLOOR |
| | PLAN. SHOW COMPLIANCE WITH SEC. 420.2 FBC. 5TH EDITION. |
| | RESPONSE: (A) THE NEW TENANT SEPARATION WALL ASSEMBLY |
| | U474 SUBMITTED IS FOR AN EXTERIOR WALL. NEED TENANT |
| | SEPARATION WALL ASSEMBLY FOR AN INTERIOR APPLICATION AS |
| | SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | (B) THE NEW TENANT SEPARATION WALL DETAIL SUBMITTED |
| | DOESN'T MATCH FLOOR PLAN. FLOOR PLAN SHOWS TWO WALLS. |
| | CLARIFY/REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW THE EXTERIOR WALL DOOR OPENING IS GOING TO BE |
| | CLOSED WITH "DRYWALL" TO SHOW COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. 1609 FBC. |
| | RESPONSE: BLOCK-UP DETAIL IS INCOMPLETE. MISSING A LOT |
| | OF INFORMATION. PROVIDE A COMPLETE WALL ASSEMBLY THAT |
| | MATCHES FLOOR PLAN. FLOOR PLAN SHOWS TWO WALLS. |
| | CLARIFY/REVISE AS REQUIRED TO MATCH. CLEARLY SPECIFY |
| | ALL CONNECTORS. METAL STRAPS IS NOT ENOUGH INFORMATION. |
| | ALSO, THIS IS AN EXTERIOR WALL. INFORMATION SUBMITTED |
| | DON'T COMPLY FOR AN EXTERIOR WALL ASSEMBLY. CLEARLY |
| | PROVIDE SPECIFICATIONS FOR THE INTERIOR SIDE AND |
| | EXTERIOR SIDE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE TEMPERATURE CONTROL FOR THE NEW |
| | BEDROOM AS REQUIRED BY SEC. 1204 FBC. |
| | RESPONSE: FLOOR PLAN SHOWS NEW WALL AC. THIS DOESN'T |
| | SATISFY THE HEATING REQUIREMENT. PLANS CALL ONLY FOR |
| | AC. ALSO, THERE IS NO DEDICATED OUTLET SHOWN FOR THE |
| | HEATING UNIT.. NOTE: HEATING IS MANDATORY, COOLING IS |
| | NOT. THE UNIT MAY BE AN A/C UNIT WITH HEAT.BUT, PLANS |
| | NEED TO SPECIFY IT AND CORRESPONDENT DEDICATED OUTLET |
| | IS REQUIRED. PROVIDE MANUFACTURER'S SPECS FOR SELECTED |
| | A/C WITH HEAT AND REVISE PLANS AS REQUIRED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |