| 2015-08-26 13:08:30 | RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- THE 2014 FBC TOOK EFFECT ON JUNE 30TH, 2015. PERMIT |
| | APPLICATION WAS SUBMITTED ON JUNE 30TH, THEREFORE THE |
| | CODE IN EFFECT IS THE 2014 FBC. ENGINEER TO REVISE |
| | PLANS AS REQUIRED. |
| | |
| | 2- THERE ARE SEVERAL BUILDINGS IN THIS PARCEL. PROVIDE |
| | A KEY PLAN SHOWING SPECIFIC BUILDING WHERE WORK IS |
| | TAKEN PLACE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- THIS IS AN APARTMENT BUILDING WITH MORE THAN 2 |
| | UNITS. THIS IS NOT OCCUPANCY GROUP R3. SEE SEC. 310.3 |
| | FBC AND REVISE AS REQUIRED. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR , MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. . REVISE VALUATION AND PROVIDE COPY OF |
| | SIGNED CONTRACT THAT SHOWS ALL THE SCOPE OF WORK. |
| | |
| | 5- NEED NOC. SEC. 713 F.S. |
| | |
| | 6- NEW BEDROOM WAS CREATED. SPECIFY COMPLIANCE WITH THE |
| | EMERGENCY EGRESS REQUIREMENTS OF SEC. 1029 FBC. |
| | |
| | 7- WALL TYPES. ACCORDING TO CITY RECORDS, THE EXTERIOR |
| | WALL OF THIS BUILDING IS NOT WOOD FRAME. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | NEW TENANT SEPARATION WALL THAT MATCHES PROPOSED FLOOR |
| | PLAN. SHOW COMPLIANCE WITH SEC. 420.2 FBC. |
| | |
| | 9- PROVIDE COMPLETE DETAILS AN SPECIFICATIONS FOR THE |
| | NEW DRYWALL PARTITION THAT MATCHES PROPOSED FLOOR PLAN |
| | AT THE PERIMETER OF THE DWELLING UNIT AND BETWEEN |
| | EXISTING BEDROOM AND EXISTING LIVING/DINING AREA. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW THE EXTERIOR WALL DOOR OPENING IS GOING TO BE |
| | CLOSED WITH "DRYWALL" TO SHOW COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. 1609 FBC. |
| | |
| | 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE TEMPERATURE CONTROL FOR THE NEW |
| | BEDROOM AS REQUIRED BY SEC. 1204 FBC. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |