| Plan Review Notes For Permit 15061430 |
| Permit Number |
15061430 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-28 11:26:27 | 1) THE ARCHITECTURAL FLOOR PLAN ON SHEET A-1 DOES NOT | | | CORRELATE WITH THE FLOOR PLAN ON SHT. P1.1. ROOM NAMES | | | ARE DIFFERENT,THE FLOOR PLAN IS DIFFERENT.THE EXECUTIVE | | | BATHROOM IS SHOWN ON A-1 BUT IT IS SHOWN AS A STORAGE | | | ROOM WITH THE PLUMBING FIXTURES DELETED ON P1.1. SUBMIT | | | PLANS THAT MATCH. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) WATER HEATER DETAIL #2. A PAN DRAIN IS REQD. FOR THE | | | EWH. | | | 3) THE BREAK ROOM SINK SHALL COMPLY WITH THE | | | FBC-ACCESSIBILITY SEC.212.3. SHOW COMPLIANCE ON THE | | | PLANS. 2ND. REQUEST. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|