| Plan Review Notes For Permit 15061430 |
| Permit Number |
15061430 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-16 12:33:09 | 1ST REVIEW: FBC 2014 MECHANICAL | | | 7/16/15 | | | | | | 1) THE PLANS ARE UNACCEPTABLE BECAUSE THE SHEETS WERE | | | SUBMITTED LOOSELY AND UNBOUND- REFER TO SECTION | | | 107.2.1.4 WPB AMENDEMENTS TO THE FLORIDA BUILDING CODE. | | | 2) DESIGN CRITERIA: THE FLORIDA BUILDING CODES-2014 | | | FIFTH EDITION WENT INTO EFFECT JUNE 30, 2015. PLEASE | | | PROVIDE ON THE PLANS A LIST OF CURRENT CODES AND | | | STANDARDS USED IN THE DESIGN OF THE PROJECT, AND UPDATE | | | THE 2010 REFERENCE UNDER THE O/A CALCULATION TABLE ON | | | SHEET M0.1. | | | 3) M1.1: THE RETURN AIR TRANFER FROM JIM'S OFFICE TO | | | THE CORRIDOR IS NOT PERMITTED- REFER TO SECTION 601.2 | | | FBC-14 MECHANICAL. | | | 4) M1.1: SHOW THE DUCT CONNECTIONS TO THE RELOCATED | | | ERV. | | | 5) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED FOR AHU'S | | | 1-6, HOWEVER THERE ARE NO AC EQUIPMENT SCHEDULES ON THE | | | PLANS TO COMPARE THE CALCS TO. PLEASE PROVIDE THE | | | SCHEDULES ON THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|