2015-07-16 12:33:091ST REVIEW: FBC 2014 MECHANICAL
 7/16/15
  
 1) THE PLANS ARE UNACCEPTABLE BECAUSE THE SHEETS WERE
 SUBMITTED LOOSELY AND UNBOUND- REFER TO SECTION
 107.2.1.4 WPB AMENDEMENTS TO THE FLORIDA BUILDING CODE.
 2) DESIGN CRITERIA: THE FLORIDA BUILDING CODES-2014
 FIFTH EDITION WENT INTO EFFECT JUNE 30, 2015. PLEASE
 PROVIDE ON THE PLANS A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT, AND UPDATE
 THE 2010 REFERENCE UNDER THE O/A CALCULATION TABLE ON
 SHEET M0.1.
 3) M1.1: THE RETURN AIR TRANFER FROM JIM'S OFFICE TO
 THE CORRIDOR IS NOT PERMITTED- REFER TO SECTION 601.2
 FBC-14 MECHANICAL.
 4) M1.1: SHOW THE DUCT CONNECTIONS TO THE RELOCATED
 ERV.
 5) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED FOR AHU'S
 1-6, HOWEVER THERE ARE NO AC EQUIPMENT SCHEDULES ON THE
 PLANS TO COMPARE THE CALCS TO. PLEASE PROVIDE THE
 SCHEDULES ON THE PLAN.
  