Plan Review Notes
Plan Review Notes For Permit 15061414
Permit Number 15061414
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-06 09:44:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 1. THE APPLICATION IS FOR WOOD FLOORING; THE TEST
 REPORTS SUBMITTED ARE FOR PROFLEX RCU 250, 8" CONCRETE
 SLAB, QUARRY TILE FLOORING (ASTM E492) AND FOR PROFLEX
 RCU 500, 6" SLABL, QUARRY TILE (ASTM E90). FLAME SPREAD
 TEST (ASTM E84) IS FOR MSC90, RCU 250, AND LV100. IT IS
 NOT CLEAR WHICH PRODUCT IS PROPOSED.
  
 2. PROVIDE THE CONCRETE SLAB THICKNESS FOR THE PROJECT,
 FBC 1207.2, 1207.3.
  
 3. EITHER PROVIDE TEST REPORTS CONSISTENT WITH THE
 PROPOSED INSTALLATION OR PROVIDE INFORMATION (FROM
 EITHER AN ENGINEER, ARCHITECT, OR MANUFACTURER ON
 LETTERHEAD) AS TO HOW THIS APPLICATION (WOOD FLOOR, ???
 INCH CONCRETE SLAB) COMPARES TO THE TESTED ASSEMBLY.
  
  
  