| Plan Review Notes For Permit 15061414 |
| Permit Number |
15061414 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-06 09:44:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2014 | | | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | | | 1. THE APPLICATION IS FOR WOOD FLOORING; THE TEST | | | REPORTS SUBMITTED ARE FOR PROFLEX RCU 250, 8" CONCRETE | | | SLAB, QUARRY TILE FLOORING (ASTM E492) AND FOR PROFLEX | | | RCU 500, 6" SLABL, QUARRY TILE (ASTM E90). FLAME SPREAD | | | TEST (ASTM E84) IS FOR MSC90, RCU 250, AND LV100. IT IS | | | NOT CLEAR WHICH PRODUCT IS PROPOSED. | | | | | | 2. PROVIDE THE CONCRETE SLAB THICKNESS FOR THE PROJECT, | | | FBC 1207.2, 1207.3. | | | | | | 3. EITHER PROVIDE TEST REPORTS CONSISTENT WITH THE | | | PROPOSED INSTALLATION OR PROVIDE INFORMATION (FROM | | | EITHER AN ENGINEER, ARCHITECT, OR MANUFACTURER ON | | | LETTERHEAD) AS TO HOW THIS APPLICATION (WOOD FLOOR, ??? | | | INCH CONCRETE SLAB) COMPARES TO THE TESTED ASSEMBLY. | | | | | | | | | |
|