| 2015-07-07 21:16:53 | A SINGLE SET OF DRAWINGS WAS SUBMITTED, IT APPEARS THAT |
| | THIS WAS ONLY TO OBTAIN A PUNCH LIST FOR RESUBMITTAL. |
| | THE FOLLOWING CORRECTIONS TO THE NEW DRAWINGS SHALL |
| | INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: |
| | 1.NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EVERY |
| | DOOR. THIS IS IN ADDITION TO THE NEC 210.62 REQUIREMENT |
| | FOR A "SHOW WINDOW" OUTLET FOR EVERY 12' OF SHOW WINDOW |
| | OR PORTION THEREOF. |
| | 2. NEC 422.30 REQUIRES A DISCONNECT FOR THE WATER |
| | HEATER. |
| | 3. FBC & NFPA101 LIFE SAFETY CODE REQUIRE EXIT LIGHTING |
| | WHICH IS NOT INDICATED ON THE PLANS. |
| | 4. FBC & NFPA 101 LIFE SAFETY CODE HAVE EMERGENCY |
| | LIGHTING REQUIREMENTS WHICH ARE NOT INDICATED ON THE |
| | PLANS. |
| | 5. FBC-ENERGY HAS SPECIFIC LIGHTING REQUIREMENTS WHICH |
| | ARE NOT REFLECTED ON THE PLANS. |
| | 6. FBC-ENERGY HAS MANDATORY SWITCHING REQUIREMENTS |
| | WHICH ARE NOT INDICATED ON THE PLANS. |
| | |
| | PROVIDE TWO SETS OF PLANS, ONE FOR THE RECORD AND THE |
| | OTHER APPROVED PLANS SHALL REMAIN ON THE JOB AT ALL |
| | TIMES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | |