Plan Review Notes
Plan Review Notes For Permit 15061364
Permit Number 15061364
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-15 17:54:541ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15061364
 7/15/15
  
 1) DESIGN CRITERIA: PROVIDE ON THE PLANS A LIST OF
 CURRENT CODES AND STANDARDS USED IN THE DESIGN OF THE
 PROJECT- SECTION 107.2 WPB AMENDMENTS TO THE FBC-10
 BUILDING.
 2) THE PLANS DO NOT INDICATE ANY MEANS OF VENTILATION
 FOR THE WET WELL- REFER TO NFPA 820- 2012: TABLES 4.2
 COLLECTION SYSTEMS AND 9.1.1.4 MINIMUM VENTILATION
 RATES AND REVISE THE PLANS TO SHOW COMPLIANCE.
 3) THE PLANS SHOW AN ACCESS HATCH: PLEASE PROVIDE
 DIMENSIONED SECTION VIEWS AND STRUCTURAL DETAILS FOR
 INSTALLATION OF THE ACCESS LADDER.
 4) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 PUMPS TO THE ROOF STRUCTURE- SECTION 301.12 FBC-10
 MECHANICAL.
 5) BASED ON THE GEOTECHNICAL SOILS REPORT, PLEASE
 PROVIDE PIPE TRENCH CROSS-SECTION DETAILS FOR TYPICAL
 INSTALLATIONS AND HIGH WATER TABLE INSTALLATIONS (IF
 APPLICABLE) INDICATE TRENCH DIMENSIONS, PIPE EMBEDMENT
 DEPTHS, BEDDING MATERIALS AND THICKNESSES, COMPACTION
 AND BACKFILLING SPECIFICATIONS.
 6) PROVIDE STANDARD PIPE FITTING, AND PIPE SUPPORT
 DETAILS FOR THE PVC AND DUCTILE IRON PIPES- SECTION 305
 FBC-10 MECHANICAL
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  