| 2015-08-05 12:43:33 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. PLEASE DEFINE THE "*" (ASTERISKS) ON PAGE E100 | | | ELECTRICAL PLAN REVIEW NOTES. | | | 2. THE RISER DIAGRAM REFLECTS THAT PUMPS 1 & 2 ARE | | | BEING SERVED FROM THE MDP W/A NEW 400 AMP 3 PHASE | | | BREAKER VIA (3) 250 KCMIL | | | 3. ACCORDING TO YOUR LOAD CALCULATIONS ON PAGE E100 & | | | NEC 430.250 PUMPS 1 & 2 HAVE A FLC OF 302 AMP. | | | 4. INDICATE THE RATING OF THE OL DEVICES. | | | 5. ACCORDING TO NEC 430.22 (302 FLC X 125%=377.5 AMP) | | | THE MINIMUM RATED CONDUCTOR SHALL BE 400 KCMIL. | | | 6. INDICATE THE TYPE OF OCPD BEING USED. | | | 7. THE ABOVE CONDUCTOR HAS NOT YET BEEN ADJUSTED FOR | | | VOLTAGE DROP. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|