Plan Review Notes
Plan Review Notes For Permit 15061364
Permit Number 15061364
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-05 12:43:33PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PLEASE DEFINE THE "*" (ASTERISKS) ON PAGE E100
 ELECTRICAL PLAN REVIEW NOTES.
 2. THE RISER DIAGRAM REFLECTS THAT PUMPS 1 & 2 ARE
 BEING SERVED FROM THE MDP W/A NEW 400 AMP 3 PHASE
 BREAKER VIA (3) 250 KCMIL
 3. ACCORDING TO YOUR LOAD CALCULATIONS ON PAGE E100 &
 NEC 430.250 PUMPS 1 & 2 HAVE A FLC OF 302 AMP.
 4. INDICATE THE RATING OF THE OL DEVICES.
 5. ACCORDING TO NEC 430.22 (302 FLC X 125%=377.5 AMP)
 THE MINIMUM RATED CONDUCTOR SHALL BE 400 KCMIL.
 6. INDICATE THE TYPE OF OCPD BEING USED.
 7. THE ABOVE CONDUCTOR HAS NOT YET BEEN ADJUSTED FOR
 VOLTAGE DROP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  