| 2015-07-23 07:08:41 | 1) UNITS #321 & #323 - ONE OF THE EXISTING COMMON AREA |
| | TOILET ROOMS IS NOW BEING CONVERTED TO A TOILET ROOM IN |
| | A PRIVATE OFFICE. A MINIMUM OF ONE WATER CLOSET AND ONE |
| | LAVATORY EACH IS REQUIRED FOR MALES AND FEMALES PER |
| | 2010 FBC-PLUMBING TABLE 403.1.THE SPACE IS NOW |
| | DEFICIENT OF THE REQUIRED MINIMUM FIXTURES. |
| | 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED |
| | WITHIN THIS SPACES #305/307 & 321/323 PER THE FBC- |
| | PLUMBING TABLE 403.1 AND THE FBC- ACCESSIBILITY SEC. |
| | 211.2. SHOW THE LOCATIONS AND CLEAR FLOOR SPACE |
| | REQUIRED BY FAC SEC.305. ALSO,THE DRINKING FOUNTAINS |
| | SHALL COMPLY WITH FAC SEC. 307. |
| | 3) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS |
| | FOR THE SHOWER STEAM UNIT. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 4) THE CONFERENCE ROOM SINK SHALL COMPLY WITH FAC SEC.S |
| | 212 & 606.2, 606.3, 606.4, 606.5. |
| | 5) SHT. A-5 NOTES THAT HANDICAP ACCESSORIES SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE 1997 FL. ACCESSIBILITY |
| | CODE. THE CODE IN EFFECT IS THE 2010 FBC- |
| | ACCESSIBILITY. REVISE THE NOTE AND SHOW ALL MOUNTING |
| | HEIGHTS. |
| | 6) SUBMIT A SANITARY AND WATER RISER DIAGRAM PER WPB |
| | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| | 7) SHT. M2.1 - REFERENCE NOTE # 2 STATES THAT THE |
| | CONDENSATE PIPING IS TO DISCHARGE TO PLUMBING DRAINS. |
| | UNCOMTAMINATED CLEAR WATER WASTE SHALL NOT DISCHARGE TO |
| | THE SANITARY SEWER SYSTEM PER CITY OF WPB CODE OF |
| | ORDINANCES SEC. 90-203. |
| | 8) REINFORCEMENT FOR GRAB BARS IS REQUIRED IN THE |
| | TOILET ROOM AND THE SHOWER IN TOM'S ROOM PER THE 2010 |
| | FBC-ACCESSIBILITY SEC.604.5 EXCEPTION # 1& 608.3. SEE |
| | EXCEPTION # 1. |
| | 9) THE DOOR FOR THE TOILET ROOM IN TOM'S ROOM SHALL |
| | NOTSWING INTO THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET PER THE 2010 FBC -ACCESSIBILITY SEC.603.2.3. SEE |
| | EXCEPTION # 1. |
| | 10) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET IN THE TOILET ROOM IN TOM'S ROOM PER THE 2010 |
| | FBC- ACCESSIBILITY SEC. 604.3. |
| | 11) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF THE |
| | SHOWER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 12) SHOWER CONTROLS SHALL COMPLY WITH FBC-ACCESSIBILITY |
| | SEC.608.5.2 & 309.4. |
| | 13) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED IN |
| | SPACES 305 & 307 PER THE FBC-PLUMBING TABLE 403.1 & |
| | FBC-ACCESSIBILITY SEC. 211.2. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |