| 2015-07-10 15:46:44 | 1ST REVIEW: FBC 2010 MECHANICAL, FBC-10 EXISTING |
| | BUILDING CODE |
| | PERMIT #15061362 |
| | 7/10/15 |
| | |
| | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | RE-CONFIGURED TENANT SPACES IN COMPLIANCE WITH SECTION |
| | 709.1 FBC-10 EXISTING BUILDING CODE, AND TABLE 403.3 |
| | FBC-10 MECHANICAL. PROVIDE A TABLE ON THE PLAN |
| | INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR |
| | AIR. |
| | 2) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR |
| | THE NEW HEAT PUMP SYSTEMS IN ACCORDANCE WITH ACCA |
| | MANUAL N OR THE ACCA/ASHRAE STANDARD 183- SECTION |
| | 503.2.1 1 FBC-10 ENERGY CONSERVATION. |
| | 3) SHEET M2.1: REFERENCE NOTE NUMBER SYMBOLS 4, 5, & 6 |
| | ARE NOT SHOWN ON THE PLANS. IT APPEARS NOTE # 5 MAY NOT |
| | BE APPLICABLE TO THE PROJECT. |
| | 4) M2.1: NOTE #2 INDICATES DISCHARGING THE THE FAN COIL |
| | UNIT CONDENSATE INTO PLUMBING DRAINS. PLEASE NOTE THAT |
| | UNCONTAMINATED COOLING WATER IS NOT PERMITTED TO DRAIN |
| | INTO THE CITY SANITARY SEWER PER SEC. 90-203 WPB CODE |
| | OF ORDINANCES. PROVISE AN APPROVED ALTERNATE LOCATION. |
| | 5) M3.2: REMOVE THE RTU CURB DETAIL- IT IS NOT |
| | APPLICABLE TO THIS PROJECT. IN IT'S PLACE PLEASE |
| | PROVIDE ENGINEERED STRUCTURAL AND WIND LOAD TIE DOWN |
| | DETAILS FOR ANCHORING THE CONDENSER ROOF STANDS AND |
| | MOUNTING THE CONDENSERS TO THE STANDS- SECTION 301.12 |
| | FBC-10 MECHANICAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |