| 2015-07-23 19:38:41 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. THE PLANS ARE TOO CLUTTERED FOR THE AMOUNT OF | | | INFORMATION PROVIDED. | | | 2. THE FLOOR PLAN DOES NOT INDICATE THE LOCATION OF THE | | | TWO REQUIRED WATER COOLERS. | | | 3. THE PANELS SCHEDULES DO NOT REFLECT THE CIRCUITS FOR | | | THE TWO REQUIRED WATER COOLERS. | | | 4. THE ELECTRIC WATER HEATER SHOWN ON SHEET P1, IS NOT | | | SHOWN ON THE ELECTRICAL FLOOR PLANS NOR IN THE PANEL | | | SCHEDULES. | | | 5. ADDITIONAL DEFICIENCIES MAY BE NOTED WHEN PLANS ARE | | | SUBMITTED IN PROPER SIZE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | |
|