| Date |
Text |
| 2015-10-28 17:22:04 | FAILURE TO SUBMIT THE REQUIRED NARRATIVE PROMPTED ME TO |
| | PERFORM A COMPLETE REVIEW OF THE PLANS FOR THE ABOVE |
| | MENTIONED PERMIT APPLICATION FOR COMPLIANCE WITH THE |
| | 2008 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); |
| | 2010 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS |
| | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. |
| | |
| | 1. PADDLE FAN OUTLET BOXES SHALL COMPLY W/NEC 314.27(D) |
| | AND SUPPORT THE SPECIFIC WEIGHT. |
| | 2. FBC-ENERGY CONSERVATION CODE SECTION 402.4.5 |
| | RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND SEALED TO REDUCE |
| | TRANSMISSION OF AIR BETWEEN IT AND THE CEILING SURFACE. |
| | 3. BATHROOM 3 LIGHT SHOULD ALSO BE CONTROLLED FROM THE |
| | BEDROOM ENTRY DOOR ON A 3 WAY SWITCH. |
| | 4. ALL LUMINAIRE OUTLETS ON WALLS OR CEILINGS SHALL |
| | ABIDE BY THE REQUIREMENTS OF NEC 314.27. |
| | 5. AS PER NEC 210.52(A) THERE IS A MISSING OUTLET ON |
| | ONE OF THE KITCHEN WALLS. |
| | 6. NEC 210.70(A)(3) REQUIRES A LIGHT INSIDE THE AUX. |
| | CLOSET ADJACENT TO THE MASTER WATER CLOSET (TOILET) FOR |
| | SERVICING THE EQUIPMENT INSIDE. |
| | 7. MARK THE LOCATION OF THE METER, MAIN DISCONNECT AND |
| | PANELS A & B ON THE FLOOR PLAN. |
| | 8. MARK THE LOCATION OF THE WATER HEATERS ON THE FLOOR |
| | PLAN. |
| | 9. MASTER BATHROOM SPA OUTLET SHALL BE MARKED ON THE |
| | FLOOR PLAN AND BE ON A GFCI PROTECTED CIRCUIT AND BE |
| | ACCESSIBLE. REMEMBER THAT THERE SHALL BE AN ACCESS |
| | OPENING LARGE ENOUGH TO REMOVE THE PUMP MOTOR W/O |
| | HAVING TO TEAR ANY OF THE WALL. |
| | 10. THE CENTRAL VACUUM CLEANER SYSTEM SHALL BE MARKED |
| | ON THE FLOOR PLAN. EVERY OUTLET SHALL BE INDICATED ON |
| | THE PLANS AND BE CONNECTED TO THE EQUIPMENT GROUND AS |
| | INDICATED IN NEC 422.15 |
| | 11. MAIN DISCONNECT SHALL HAVE LUGS LISTED FOR |
| | MULTI-CONDUCTOR AS STATED IN NEC 110.14. |
| | 12. INTER-SYSTEM BONDING LUGS AS INDICATED IN NEC |
| | 250.94 SHALL BE PROVIDED. |
| | 13. CORRECT FEEDER LABELS TO PANELS A & B. 3 3/0 & 1 #4 |
| | IN EACH, AS THERE IS A FEEDER FOR EACH PANEL. THIS |
| | WORDING IS MISLEADING; INDICATIVE OF FEEDERS TO PANEL A |
| | AND THEN FEEDING B FROM IT. YET THE DIAGRAM SHOWS ONE |
| | TO EACH. |
| | 14. POOL AND ALL ASSOCIATED ELECTRIC SHALL BE UNDER A |
| | SEPARATE PERMIT WITH A SEPARATE SUBMITTAL PACKAGE. |
| | 15. CORRECT CONDUCTOR INSULATION NOTE. CONDITIONS AND |
| | NOT SIZING DICTATE CONDUCTOR INSULATION REQUIREMENTS. |
| | 16. NOTE 16 STATES THAT GAS APPLIANCES ARE IN USE. THIS |
| | IS CONTRARY TO INDICATIONS IN ELECTRICAL PANEL |
| | SCHEDULES. CORRECT ACCORDINGLY. |
| | 17. RECEPTACLE OUTLETS SHALL BE TAMPER-RESISTANT ?TR? |
| | AS INDICATED IN NEC 406.11. |
| | 18. ARC-FAULT REQUIREMENTS ARE DICTATED IN NEC 210.12. |
| | 19. YOU SHALL SUBMIT LOAD CALCS FOR EACH PANEL. |
| | |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. |
| | WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED WITH |
| | THE STANDARD CITY RE-SUBMITTAL FORM. |
| | PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |