Plan Review Notes
Plan Review Notes For Permit 15061348
Permit Number 15061348
Review Stop E
Sequence Number 2
Notes
Date Text
2015-10-28 17:22:04FAILURE TO SUBMIT THE REQUIRED NARRATIVE PROMPTED ME TO
 PERFORM A COMPLETE REVIEW OF THE PLANS FOR THE ABOVE
 MENTIONED PERMIT APPLICATION FOR COMPLIANCE WITH THE
 2008 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE);
 2010 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. PADDLE FAN OUTLET BOXES SHALL COMPLY W/NEC 314.27(D)
 AND SUPPORT THE SPECIFIC WEIGHT.
 2. FBC-ENERGY CONSERVATION CODE SECTION 402.4.5
 RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND SEALED TO REDUCE
 TRANSMISSION OF AIR BETWEEN IT AND THE CEILING SURFACE.
 3. BATHROOM 3 LIGHT SHOULD ALSO BE CONTROLLED FROM THE
 BEDROOM ENTRY DOOR ON A 3 WAY SWITCH.
 4. ALL LUMINAIRE OUTLETS ON WALLS OR CEILINGS SHALL
 ABIDE BY THE REQUIREMENTS OF NEC 314.27.
 5. AS PER NEC 210.52(A) THERE IS A MISSING OUTLET ON
 ONE OF THE KITCHEN WALLS.
 6. NEC 210.70(A)(3) REQUIRES A LIGHT INSIDE THE AUX.
 CLOSET ADJACENT TO THE MASTER WATER CLOSET (TOILET) FOR
 SERVICING THE EQUIPMENT INSIDE.
 7. MARK THE LOCATION OF THE METER, MAIN DISCONNECT AND
 PANELS A & B ON THE FLOOR PLAN.
 8. MARK THE LOCATION OF THE WATER HEATERS ON THE FLOOR
 PLAN.
 9. MASTER BATHROOM SPA OUTLET SHALL BE MARKED ON THE
 FLOOR PLAN AND BE ON A GFCI PROTECTED CIRCUIT AND BE
 ACCESSIBLE. REMEMBER THAT THERE SHALL BE AN ACCESS
 OPENING LARGE ENOUGH TO REMOVE THE PUMP MOTOR W/O
 HAVING TO TEAR ANY OF THE WALL.
 10. THE CENTRAL VACUUM CLEANER SYSTEM SHALL BE MARKED
 ON THE FLOOR PLAN. EVERY OUTLET SHALL BE INDICATED ON
 THE PLANS AND BE CONNECTED TO THE EQUIPMENT GROUND AS
 INDICATED IN NEC 422.15
 11. MAIN DISCONNECT SHALL HAVE LUGS LISTED FOR
 MULTI-CONDUCTOR AS STATED IN NEC 110.14.
 12. INTER-SYSTEM BONDING LUGS AS INDICATED IN NEC
 250.94 SHALL BE PROVIDED.
 13. CORRECT FEEDER LABELS TO PANELS A & B. 3 3/0 & 1 #4
 IN EACH, AS THERE IS A FEEDER FOR EACH PANEL. THIS
 WORDING IS MISLEADING; INDICATIVE OF FEEDERS TO PANEL A
 AND THEN FEEDING B FROM IT. YET THE DIAGRAM SHOWS ONE
 TO EACH.
 14. POOL AND ALL ASSOCIATED ELECTRIC SHALL BE UNDER A
 SEPARATE PERMIT WITH A SEPARATE SUBMITTAL PACKAGE.
 15. CORRECT CONDUCTOR INSULATION NOTE. CONDITIONS AND
 NOT SIZING DICTATE CONDUCTOR INSULATION REQUIREMENTS.
 16. NOTE 16 STATES THAT GAS APPLIANCES ARE IN USE. THIS
 IS CONTRARY TO INDICATIONS IN ELECTRICAL PANEL
 SCHEDULES. CORRECT ACCORDINGLY.
 17. RECEPTACLE OUTLETS SHALL BE TAMPER-RESISTANT ?TR?
 AS INDICATED IN NEC 406.11.
 18. ARC-FAULT REQUIREMENTS ARE DICTATED IN NEC 210.12.
 19. YOU SHALL SUBMIT LOAD CALCS FOR EACH PANEL.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW.
 WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED WITH
 THE STANDARD CITY RE-SUBMITTAL FORM.
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  