| Notes |
| Date |
Text |
| 2015-07-22 08:54:19 | 7/22/15 PLUMBING REVIEW DENIED | | | | | | | | | FBC 2010 | | | | | | 1.LAUNDRY SINK AND WASHING MACHINE MUST TIE INTO | | | BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP. FBCR | | | P3108.1 | | | | | | 2. WATER CLOSET AND BIDET IN MASTER BATHROOM NOT VENTED | | | MUST TIE INTO BATHROOM GROUP. FBC P3105.1 | | | | | | 3.ALL SINKS AND LAVATORY'S MUST BE VENTED. FBC | | | P3101.2.1 | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6611 | | | [email protected] |
|