| 2015-08-26 08:14:24 | 1ST REVIEW: FBC 2010 RESIDENTIAL |
| | PERMIT #15061348 |
| | 8/26/15 |
| | |
| | 1) THE SUBMITTED SOIL TESTING AND ENGINEERING REPORT |
| | FROM ALTERRA IS INCOMPLETE (SUBJECT: DEMUCKING |
| | INTERVENTION). REFER TO PARAGRAPH 2 OF THE COVER LETTER |
| | AND SUBMIT COPIES OF THE FEBRUARY/2015 GEOTECHNICAL |
| | REPORT WHICH, ACCORDING TO THE LETTER, PROVIDES |
| | "RECOMMENDATIONS FOR BEARING-GRADE PREPARATION" OF THE |
| | SOIL. THE COMPLETE REPORT SHALL INCLUDE AMONG OTHER |
| | THINGS, A DIMENSIONED DRAWING OF THE AREA(S) OF THE LOT |
| | THAT WERE DEMUCKED (WAS THE POOL INCLUDED?), THE CLEAN |
| | SAND FILL AND COMPACTION PROCEDURE, AND ESTABLISH THE |
| | LOAD BEARING VALUE OF THE SOIL- REFER TO SECTIONS |
| | R401.4 AND R506 FBC-10 RESIDENTIAL |
| | 2) REFER TO SECTION R802.1.6.1 AND SUBMIT TWO COPIES OF |
| | THE ROOF TRUSS DESIGN DRAWINGS. |
| | 3) REFER TO TABLE R301.2(2) AND CORRECT THE COMPONENT |
| | AND CLADDING WIND PRESSURES (ULTIMATE DESIGN WIND |
| | SPEED). PLEASE INCLUDE THE MEAN ROOF HEIGHT. |
| | 4) SHEET S-0: PROVIDE NOTES AND DETAILS FOR |
| | FIREBLOCKING AND DRAFTSTOPPING- REFER TO SECTIONS |
| | R302.11 & R302.12. |
| | 5) SHEET S-1: REFER TO THE SURVEY AND PROVIDE THE |
| | FINISH FLOOR ELEVATION ON THE DRAWING. |
| | 6) S-1: REFER TO SECTION R506.2.3 AND INDICATE THE TYPE |
| | AND THICKNESS OF THE SLAB VAPOR BARRIER. |
| | 7) S-1: REFER TO SECTION R506.2.5 AND INDICATE THE TYPE |
| | OF SLAB REINFORCEMENT TO BE INSTALLED. IF WIRE MESH IS |
| | TO BE INSTALLED PROVIDE DETAILS INDICATING THE TYPE AND |
| | SIZE OF WIRE, AND HOW THE WIRE WILL BE SUPPORTED AND |
| | LAPPED. |
| | 8) INDICATE THE AREAS OF THE SLAB WHERE CRACK BARS WILL |
| | ME INSTALLED AND PROVIDE DETAILS IF APPLICABLE. |
| | 9) S-1: & S3.: PROVIDE A DETAIL AND SYMBOL FOR THE |
| | RECESSED SHOWER SLABS. |
| | 10) S-2.1: THE 8"X12" TB #2 OVER THE 18'0" GARAGE DOOR |
| | OPENING IS OVERSPANNED PER TABLE R611.8. PLEASE |
| | CORRECT. |
| | 11) S-3.3: THE WINDOW AND DOOR BUCK ATTACHMENT DETAILS |
| | SHOW BEVELED BUCKS WHICH ARE NOT PERMITTED PER SECTION |
| | R612.10.2.1. PLEASE CORRECT. |
| | 12) S-3.3, TYPICAL WALL SECTION: PROVIDE THE SLOPE OF |
| | THE GRADE AT THE FOUNDATION PER SECTION R401.3. |
| | 13) S-3.4: PROVIDE A DETAIL FOR L-28 AS SHOWN ON SHEET |
| | S-2.1. |
| | 14) A-1: INDICATE THE LOCATION OF THE REQUIRED ATTIC |
| | HATCH, AND PROVIDE A DETAIL FOR INSTALLATION- SECTION |
| | R807.1. |
| | 15) A-1: PROVIDE ROUGH FRAMING AND INTERIOR FINISH |
| | DETAILS FOR THE COFFERED CEILINGS. |
| | 16) A-1: "F" TYPE WINDOWS ARE SHOWN AT THE MASTER BATH, |
| | HOWEVER THEY ARE NOT INCLUDED IN THE SCHEDULE ON A7. |
| | PLEASE NOTE THAT THE F AND B TYPE WINDOWS SHALL HAVE |
| | TEMPERED GLASS -SECTION R308.4. |
| | 17) A-1: PROVIDE A SEDCTION DETAIL FOR THE |
| | GARAGE/LIVING SEPARATION WALL- SECTION R302.6. |
| | 18) A-1 & A-7: INDICATE WHICH BATHROOM DOOR IS MEETING |
| | THE MINIMUM 29 INCH CLEAR WIDTH OPENING REQUIRED BY |
| | SECTION R320.1.1. |
| | 19) A-1 & A-7: PROVIDE A COMPLETE WINDOW SCHEDULE THAT |
| | INCLUDES THE TYPES OF WINDOWS TO BE INSTALLED- IMPACT |
| | OR NON-IMPACT, WINDOW FRAME MATERIALS, WIDTH AND |
| | HEIGHT, AND THICKNESSES AND EFFICIENCY RATINGS OF THE |
| | GLASS. EGRESS WINDOWS AND THEIR CLEAR OPENING SIZES |
| | SHALL BE SHOWN IN THE SCHEDULE.- REFER TO SECTION |
| | R310.1. |
| | 20) A-4: COVERED PATIO- A BOND BREAK SHALL BE PROVIDED |
| | BETWEEN THE WATER RESISTIVE BARRIER AND THE STUCCO- |
| | REFER TO SECTION R703.6.3 AND CHOOSE ONE OF THE THREE |
| | METHODS SHOWN. PLEASE NOTE THAT HIGH RIB LATH (3/8") IS |
| | REQUIRED FOR CEILING INSTALLATIONS PER THE ASTM C1063 |
| | STANDARD. |
| | 21) A-4: PROVIDE ROUGH FRAMING AND EXTERIOR FINISH |
| | DETAILS FOR THE COVERED ENTRY AND OUTDOOR KITCHEN |
| | CEILINGS. |
| | 22) A- 6: PROVIDE ATTIC VENTILATION CALCULATIONS IN |
| | ACCORDANCE WITH SECTIONS R806.1 & R806.2. |
| | 23) E-1: CARBON MONOXIDE DETECTORS SHALL BE INSTALLED |
| | WITHIN 10' OF EACH BEDROOM- SECTION R315.1. |
| | 24) PRODUCT APPROVALS REQUIRED BUT NOT INCLUDED IN THE |
| | SUBMITTAL PACKAGE: |
| | A) ROOF TILE AND INSTALLATION COMPONENTS- UNDERLAYMENT, |
| | FOAM ADHESIVE- IF TO BE USED. |
| | B) #1 FOYER DOOR. |
| | C) #12 MASTER BEDRM WOOD FRAME ENTRY DOOR. |
| | D) #17 BREAKFAST WOOD FRAME ENTRY DOOR. |
| | E) #20 CABANA WOOD FRAME ENTRY DOOR. |
| | F) #30 GARAGE METAL FRAME ENTRY DOOR. |
| | PLEASE NOTE IN REGARD TO THE SUBMITTAL PACKAGE: A) ALL |
| | SUBMITTALS FOR WINDOWS AND DOORS ARE PGT "ALUMINUM" |
| | WHICH IS IN CONFLICT WITH THE SCHEDULES- PLEASE |
| | CORRECT. B) DUPLICATE COPIES OF THE WINDOW AND DOOR |
| | PRODUCT APPROVALS (EXCEPT GARAGE) WERE NOT SUBMITTED. |
| | C) ALL PRODUCT APPROVALS OR NOA'S MUST BE REVIEWED AND |
| | APPROVED BY THE DESIGN PROFESSIONAL RECORD WHO SHALL |
| | CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL APPLICABLE |
| | INSTALLATION NOTES AND DETAILS, FRAME AND GLASS TYPES, |
| | DESIGN PRESSURES, ANCHORS ETC. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |