2016-01-07 13:51:592ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061339
 01/07/16
  
 1) THE RE-SUBMITTED PLANS INDICATE A NEW AC SYSTEM FOR
 THE STAGING AREA: A) PROVIDE AC COOLING AND HEATING
 CALCULATIONS- SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION. B) PROVIDE ENERGY CALCULATIONS- SECTION
 101.5 FBC-10 ENERGY CONSERVATION.
 2) SHOW THE CONDENSATE PIPING RUN AND DISCHARGE
 LOCATION- SECTION 307.2.1 FBC-10 MECHANICAL.
 3) HOW IS MAKE-UP AIR BEING PROVIDED FOR THE BATH
 EXHAUST SYSTEM- SECTION 501.3 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER