| Plan Review Notes For Permit 15061339 |
| Permit Number |
15061339 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-23 04:37:31 | 1) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF THE TOILET | | | ROOM. A MINIMUM OF 85 INCHES IN WIDTH IS REQUIRED. 2010 | | | FBC-ACCESSIBILITY SEC.604.3, FBC-PLUMBING SEC. 405.3.1. | | | 2) SHT.A-1.01 - THE GRAB BARS SHALL BE MEASURED TO THE | | | TOP OF GRIPPING SURFACE, NOT TO THE CENTERLINE FROM THE | | | FINISH FLOOR PER 2010 FBC-ACCESSIBILITY SEC. 609.4. | | | 3) SHT. A-1.01 - THE TOILET PAPER DISPENSER SHALL BE | | | LOCATED 7-9 INCHES IN FRONT OF THE WATER CLOSET PER | | | 2010 FBC -ACCESSIBILITY SEC.604.7. | | | 4) SHT. P-2 - A SHUTOFF VALVE IS REQUIRED ON THE HOSE | | | BIBB. 2010 FBC-PLUMBING SEC.606.2. | | | 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR | | | THE EEMAX TANKLESS WATER HEATER. WPB AMEND. TO 2010 FBC | | | SEC. 107.2.1. | | | 6) WHAT IS THE PURPOSE OF THE 3-COMPARTMENT SINK? IS | | | THE SINK NEW OR EXISTING? WHAT IS BEING DISCHARGED INTO | | | THE FIXTURE? IS THERE AN EXISTING GREASE TRAP FOR THIS | | | STORE? IF ANY TYPE OF GREASY WASTE IS BEING DISCHARGED | | | INTO THE 3 COMPARTMENT SINK, A GREASE TRAP OR GREASE | | | INTERCEPTOR MAY BE REQUIRED. IF THERE IS AN EXISTING | | | GREASE TRAP, SHOW THE LOCATION ON THE SITE PLAN. 2010 | | | FBC -PLUMBING, SEC.1003.3.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|