| 2015-07-09 15:19:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE SUBMITTED WERE LOOSE, NOT ORGANIZED AND NOT |
| | BOUND PER SET. PLEASE BIND ON THE RESUBMITTAL. |
| | |
| | 2) COVER SHEET - INDICATES INCORRECT CODES. THE |
| | PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH |
| | EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING THE |
| | 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 3) SHEET A 0.00 & E2 - ADD TWO (2) EXIT SIGNS ON EACH |
| | SIDE OF THE MARKET PLACE TOWARDS THE CENTER LEADING AND |
| | DIRECTING OUT FROM THE BACK CORNER AND FROM THE CENTER |
| | LEADING AND DIRECTING TO THE REAR CORRIDOR AND EXIT. |
| | |
| | 4) SHEET A1.01 - INDICATES TWO EXIT DOORS WITH PANIC |
| | HARDWARE AND SECURITY LOCKS. THEY SHALL COMPLY WITH |
| | NFPA 101, CHAPER 36, 36..2.2.2 AND CHAPTER 7. |
| | 7.2.2.1.5.5 , THE DOOR HAVE HAVE AN INTERIOR KEYED DOOR |
| | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. THE KEYED LOCK TO BE EQUIPPED WITH AN |
| | ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 |
| | OR SIMILAR). |