| 2015-07-17 12:13:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15061339 |
| | ADD: 5209 BROADWAY |
| | CONT: PROFESSIONAL FINISHES |
| | TEL: ( 561)746-1517 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 17/2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 0.00 DETAIL # 6 SHOWS A 36 TALL SIGNAGE |
| | STRUCTURE ATTACHED TO THE EXISITNG CONCRETE BEAM. |
| | REFERS TO STRUCTURAL SHEET. SHEET S-1 DOES NOT HAVE ANY |
| | SUCH DETAILS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | EQUIRED FOR ATTACHMENT AND WIND LOADING, TYPE OF |
| | MATERIALS. |
| | |
| | 2) SHEET A-0.00 INDICATES NEW OPENINGS AND OR |
| | REPLACEMENT OF 1) EXTERIOR DOORS, 2) OVERHEAD COUNTER |
| | ROLL UP WINDOW & 3) GLASS BLOCKWINDOWS. THIS REVIEW NO |
| | SUCH PRODUCT APPROVALS WERE SUBMITTED. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) NO WIND DESIGN CRITERIA AND PRESSURES HAS BEEN |
| | PROVIDED FOR THE NEW OR REPLACEMENT OPENINGS. |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |