| Plan Review Notes For Permit 15061338 |
| Permit Number |
15061338 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-21 10:50:57 | 1) SHOW THE WIDTH OF THE HANDICAP ACCESSIBLE TOILET | | | ROOMS. THE MINIMUM WIDTH SHALL BE 85" IF BUILT PERFECT, | | | 86 INCHES ALLOWS FOR TOLERANCE. | | | 2) THE ARCHITECTURAL PLANS ARE NOT SIGNED AND SEALED BY | | | THE DESIGN PROFESSIONAL OF RECORD AS REQUIRED BY FL. | | | ADMIN. CODE RULE 61G1-16.003. | | | 3) SHT. P1.1 - SHOWS THE USE OF AN AIR ADMITTANCE | | | VALVE. WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN | | | FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK, THE | | | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT | | | INSTALLED IN ACCORDANCE WITH 2010 FL. PLUMBING CODE | | | SEC.917.3.2.CLARIFY WHERE THE NEW SANITARY LINE WILL | | | CONNECT TO THE EXISTING. | | | 4) THE BACK TO BACK LAVATORIES ON THE RISER DIAGRAM ARE | | | NOT VENTED.FPC 901.2.1. | | | 5) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATERS.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|