| Plan Review Notes For Permit 15061338 |
| Permit Number |
15061338 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-19 11:53:35 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15061338 | | | 8/19/15 | | | | | | 1) SHEET M2.01: PLEASE CLARIFY KEY NOTE #1. IS THE | | | EXHAUST CONNECTING TO AN EXISTING EXHAUST RISER? | | | 2) M4.01: AHU/CU 1-1A AT 4.0 TONS OF COOLING IS | | | OVERSIZED PER THE SUBMITTED TRACE CALCULATION WHICH IS | | | INDICATING ONLY 3.0 TONS OF COOLING FOR ZONE 1B- REFER | | | TO SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|