| Plan Review Notes For Permit 15061338 |
| Permit Number |
15061338 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-28 20:02:52 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. YOU SHALL SUBMIT A FIXTURE SCHEDULE TO DETERMINE THE | | | EXTENT OF EMERGENCY LIGHTING PROVIDED BEYOND THE COUPLE | | | OF BUG-EYE FIXTURES. | | | 2. YOU SHALL PROVIDE INTERIOR EXIT LIGHTING TO INDICATE | | | THE PATH OF EGRESS. | | | 3. SUBMIT A LIGHT DENSITY CHART IN COMPLIANCE WITH | | | FBC-ENERGY CONSERVATION. | | | 4. WHETHER A MODEL OR ACTUAL, KITCHEN OUTLETS SHALL | | | COMPLY WITH NEC 210.52(B). | | | 5. THE OTHER MODEL UNITS SHALL ALSO HAVE THE PROPER | | | OUTLET SPACING AND MEET MINIMUM LIGHTING REQUIREMENTS | | | AS WELL. | | | 6. THERE SHALL BE A SERVICE OUTLET WITHIN 25? OF THE | | | HVAC UNIT PER NEC 210.63 | | | 7. PROVIDE LOAD CALCS & BETTER DEFINE THE RAISER | | | DIAGRAM | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|