Plan Review Notes
Plan Review Notes For Permit 15061338
Permit Number 15061338
Review Stop E
Sequence Number 1
Notes
Date Text
2015-09-28 20:02:52PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU SHALL SUBMIT A FIXTURE SCHEDULE TO DETERMINE THE
 EXTENT OF EMERGENCY LIGHTING PROVIDED BEYOND THE COUPLE
 OF BUG-EYE FIXTURES.
 2. YOU SHALL PROVIDE INTERIOR EXIT LIGHTING TO INDICATE
 THE PATH OF EGRESS.
 3. SUBMIT A LIGHT DENSITY CHART IN COMPLIANCE WITH
 FBC-ENERGY CONSERVATION.
 4. WHETHER A MODEL OR ACTUAL, KITCHEN OUTLETS SHALL
 COMPLY WITH NEC 210.52(B).
 5. THE OTHER MODEL UNITS SHALL ALSO HAVE THE PROPER
 OUTLET SPACING AND MEET MINIMUM LIGHTING REQUIREMENTS
 AS WELL.
 6. THERE SHALL BE A SERVICE OUTLET WITHIN 25? OF THE
 HVAC UNIT PER NEC 210.63
 7. PROVIDE LOAD CALCS & BETTER DEFINE THE RAISER
 DIAGRAM
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  