Plan Review Notes
Plan Review Notes For Permit 15061317
Permit Number 15061317
Review Stop B
Sequence Number 4
Notes
Date Text
2016-01-07 09:32:23BUILDING REVIEW APPROVED WITH PROVISO:
 1- SHEET 5 OF 6:
 A) REVISE ROOF BCLL. THE 10PSF NON-CONCURRENT LOAD
 SPECIFIED AFTER THE 20PSF IS INCORRECT. THE CORRECT
 LIVE LOAD IS 20PSF PER NOTES "B" AND "G" OF-TABLE
 R301.5.
 B) ROOF FRAMING PLAN: SPECIFY CONNECTOR AT BOTH ENDS OF
 ALL GIRDER TRUSSES.
 C) CONNECTOR #2 SPECIFIED FOR GIRDER TRUSS A15G NEEDS
 TO BE REVISED. THIS IS A TWO PLY GIRDER TRUSS. REVISE
 THE NUMBER OF CONNECTORS REQUIRED FOR A TWO PLY TRUSS
 AND SPECIFY THE CORRECT SIZE OF NAIL ACCORDING TO THE
 NUMBER OF TRUSSES. SEE PRODUCT APPROVAL FOR CONNECTOR
 HHETA AND REVISE AS REQUIRED. 1.
 2- REVISE THE EXPOSURE SPECIFIED ON THE DESIGN
 CRITERIA. BUILDING IS LOCATED IN EXPOSURE "D" NOT "B".
 SEC. R301.2.1.4.3.
 3- REVISE ENERGY CALCULATIONS:
 A) CONDITIONED AREA DOESN'T MATCH AREA SHOWN ON PLANS.
 B) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5 DOESN'T MATCH
 PLANS AND PRODUCT APPROVAL SUBMITTED.
 C) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5. THERE ARE
 NOT WOOD DOORS.
 D) ENTRY DOOR PRODUCT APPROVAL FL15210.6 SUBMITTED IS
 FOR DOORS WITH GLAZING. THIS DOORS NEED TO BE ENTERED
 IN THE WINDOWS SECTIONS NOT DOORS.
 E) COMPLETE THE FLORIDA CODE COMPLIANCE CHECKLIST PAGE
 5 OF 5.
 F) COMPLETE THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY
 CARD.
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.0002(33) FOR:
 A) PRECAST LINTELS AS SHOWN ON PLANS.
 B) SLIDING GLASS DOORS AS SHOWN ON SHEET A-3 BY THE
 DINING ROOM AREA.
 C) SINGLE HUNG WINDOWS. INFORMATION FROM JELD-WEN
 SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT APPROVAL
 NUMBER.
 D) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ITEM #6 BELOW. NOTE: SEE ROOF TILE NOA
 11-0510.02 SUBMITTED FOR LISTED ADHESIVES.
 5- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.
 6- ROOFING FINISH MATERIAL WAS CHANGED FROM SHINGLES TO
 CONCRETE TILE. DESIGNER OF RECORD TO SPECIFY HOW IS THE
 TILE GOING TO BE INSTALLED (ADHESIVE OR SCREWS/NAILS).
 7- PROVIDE 2 COPIES OF THE SOIL TEST REPORT WITH
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S.
 8- TRUSS ENGINEER TO REVISE TRUSS PACKAGE SUBMITTED:
 A) ALL INDIVIDUAL TRUSS DRAWINGS NEED A TITLE BLOCK
 WITH THE ENGINEER NAME, ADDRESS AND LICENSE NUMBER AND
 THE DATE OF THE DRAWING AS REQUIRED BY 1G15-31.003 OF
 FLORIDA ADMINISTRATIVE CODE.
 B) REVISE THE ATTIC LIVE LOAD TO COMPLY WITH FOOTNOTES
 "B" AND "G" OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 NEED 20PSF ATTIC LIVE LOAD. SEE PLANS AND TABLE R301.5.