Plan Review Notes
Plan Review Notes For Permit 15061317
Permit Number 15061317
Review Stop B
Sequence Number 3
Notes
Date Text
2015-12-30 19:07:01NEW SINGLE FAMILY RESIDENCE (R3), THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ****NOTE:
 COMMENTS BELOW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT OWNER/BUILDER MAY OBTAIN PERMIT IF OTHER
 TRADES PASS THEIR REVIEWS. AND, THE COMMENTS BELOW ARE
 ADDRESSED AFTER THE PERMIT IS ISSUED AND BEFORE
 INSPECTIONS ARE REQUIRED.. REVISION FEES WILL APPLY.
 OWNER/BUILDER TO ADVICE IF PROVISO OPTION IS PREFERRED.
  
  
 NOTE:
 PERMIT APPLICATION IS MISSING FROM PACKAGE SUBMITTED.
  
  
 1- SHEET 5 OF 6:
 A) CLEARLY SPECIFY THE ATTIC LIVE LOAD ON THE DESIGN
 CRITERIA. SEE FOOTNOTES "B" AND "G" OF TABLE R301.5 AND
 REVISE DESIGN CRITERIA AS REQUIRED.
 RESPONSE: THE ROOF BCLL WAS REVISED TO SAY 20PSF, BUT
 THERE IS A NOTE STATING THAT "10PSF BCLL
 NON-CONCURRENT". THERE IS A CONFLICT ON THIS STATEMENT.
 IF THE BCLL IS 20PSF, THEN THE NON-CONCURRENT LIVE LOAD
 IS 20PSF NOT 10PSF. REVISE AS REQUIRED.
  
 B) REVISE THE EXPOSURE SPECIFIED ON THE DESIGN
 CRITERIA. BUILDING IS LOCATED IN EXPOSURE "D" NOT "B".
 SEC. R301.2.1.4.3 OF 2010 FBC.
  
 2- TYPICAL WALL SECTION ON SHEET 3 OF 6:
 A) THERE ARE TWO DIFFERENT NAIL TYPES AND SPACING SPECS
 FOR THE ROOF SHEATHING FASTENING. REVISE AS REQUIRED.
 SEE SEC. R803.2.3.1.
 RESPONSE: WALL SECTION STILL SHOWS TWO DIFFERENT NAILS.
 10D RING SHANK NAILS AND 10D NAILS. SPECIFY ONLY ONE
 TYPE. NOTE: RING SHANK NAILS ARE REQUIRED BY SEC.
 R803.2.3.1.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY CODE COMPLIANCE AT BOTTOM OF
 FORM SUBMITTED. SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) CONDITIONED AREA DOESN'T MATCH PLANS . REVISE AS
 REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 RESPONSE: REPEAT COMMENT.
  
 C) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5 DOESN'T MATCH
 PLANS AND PRODUCT APPROVAL SUBMITTED. REVISE AS
 REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5. THERE ARE
 NOT WOOD DOORS. SEE PRODUCT APPROVAL SUBMITTED. AND,
 SEE COMMENT BELOW. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 E) ENTRY DOOR PRODUCT APPROVAL FL15210.6 SUBMITTED IS
 FOR DOORS WITH GLAZING. THIS DOORS NEED TO BE ENTERED
 IN THE WINDOWS SECTIONS NOT DOORS. SEE SEC. 405.5.3 OF
 2010 FBC-ENERGY CONSERVATION ANDS REVISE AS REQUIRED.
  
 F) COMPLETE THE FLORIDA CODE COMPLIANCE CHECKLIST PAGE
 5 OF 5 AS REQUIRED BY SEC. 405.4.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 G) COMPLETE THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY
 CARD AS REQUIRED BY SEC. 405.4.3 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.0002(33) FOR:
 A) PRECAST LINTELS AS SHOWN ON PLANS.
 RESPONSE: INFORMATION SUBMITTED IS NOT AN APPROVED
 PRODUCT APPROVAL. (REPEAT COMMENT. THREE TIMES).
  
 B) SLIDING GLASS DOORS AS SHOWN ON SHEET A-3 BY THE
 DINING ROOM AREA. THERE IS NOT PRODUCT APPROVAL FOR
 SLIDING GLASS DOORS IN THE RE-SUBMITTED PACKAGE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 C) SINGLE HUNG WINDOWS. INFORMATION FROM JELD-WEN
 SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT APPROVAL
 NUMBER. PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER
 THAT CORRESPONDS TO PACKAGE SUBMITTED.
 RESPONSE: SAME PACKAGE RE-SUBMITTED. COMMENT NOT
 ADDRESSED.
  
 D) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ITEM #6 BELOW. NOTE: SEE ROOF TILE NOA
 11-0510.02 SUBMITTED FOR LISTED ADHESIVES. PROVIDE THAT
 PRODUCT APPROVAL.
  
 5- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 6- ROOFING FINISH MATERIAL WAS CHANGED FROM SHINGLES TO
 CONCRETE TILE. DESIGNER OF RECORD NEEDS TO SPECIFY HOW
 IS THE TILE GOING TO BE INSTALLED (ADHESIVE OR
 SCREWS/NAILS) TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC. IF USING
 SCREWS/NAILS, THEN SPECIFY SIZE AND NUMBER REQUIRED TO
 MEET THE DESIGN PRESSURES.
  
 7- PROVIDE 2 COPIES OF THE SOIL TEST REPORT AS REQUIRED
 BY SEC. R401.4 OF 2010 FBC-RESIDENTIAL.
 RESPONSE: SOIL TEST REPORT SUBMITTED NEED TO HAVE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
  
 8- SHEET 5 OF 6:
 A) ROOF FRAMING PLAN IS MISSING THE CONNECTOR AT THE
 END OF SOME GIRDER TRUSSES. CIRCLE DENOTING CONNECTOR
 IS IN BLANK. SPECIFY CONNECTOR AT BOTH ENDS OF GIRDER
 TRUSSES. SEC. R301.
  
 B) CONNECTOR #2 SPECIFIED FOR GIRDER TRUSS A15G NEEDS
 TO BE REVISED. THIS IS A TWO PLY GIRDER TRUSS. REVISE
 THE NUMBER OF CONNECTORS REQUIRED FOR A TWO PLY TRUSS
 AND SPECIFY THE CORRECT SIZE OF NAIL ACCORDING TO THE
 NUMBER OF TRUSSES. SEE PRODUCT APPROVAL FOR CONNECTOR
 HHETA AND REVISE AS REQUIRED. SEC. R301.
  
 9- TRUSS ENGINEER TO REVISE TRUSS PACKAGE SUBMITTED:
 A) ALL INDIVIDUAL TRUSS DRAWINGS NEED A TITLE BLOCK
 WITH THE ENGINEER NAME, ADDRESS AND LICENSE NUMBER AND
 THE DATE OF THE DRAWING AS REQUIRED BY 1G15-31.003 OF
 FLORIDA ADMINISTRATIVE CODE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) REVISE THE ATTIC LIVE LOAD TO COMPLY WITH FOOTNOTES
 "B" AND "G" OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 NEED 20PSF ATTIC LIVE LOAD. SEE PLANS AND TABLE R301.5.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 **** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE REMOVE ANY REVISED SHEET. SUBMIT OLD COPIES
 FOR REFERENCE. DON"T STAPLE OLD COPIES TO NEW REVISED
 SET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]