2015-10-08 06:47:231) THERE ARE TWO DIFFERENT PROFESSIONAL ENGINEERS ON
 THE TITLE BLOCK.THE DRAWINGS NEED TO BE SIGNED AND
 SEALED BY THE ENGINEER RESPONSIBLE FOR EACH DESIGN
 DISCIPLINE PER FL. STATUTE 471 AND FL. ADMIN. CODE RULE
 61G15-23.002.
 2) SHT. A-8 IS MISSING FROM ONE SET OF PLANS. SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB AMEND. TO
 FBC SEC.107.1.
 3) SUBMIT A SANITARY RISER DIAGRAM THAT IS CODE
 COMPLIANT AND CORRELATES WITH THE FLOOR PLAN. WPB
 AMEND. TO FBC SEC. 107.3.5.3.
 4) SHT. A-8 SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD. FL. ADMIN. CODE RULE
 61G15-23.002.
 5) SHT. A-3 - THE SEAL FROM FROM JOHN HOLT HAS BEEN
 PASTED ONTO THE PLAN.THIS VIOLATES FL> ADMIN. CODE
 61G15-23.002. PLANS SHALL BEAR THE SIGNATURE AND SEAL
 OF THE DESIGN PROFESSIONAL.
  