| 2015-11-16 09:45:52 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15061317 |
| | 11/16/15 |
| | |
| | 1) THE FOLLOWING DOCUMENTS ARE MISSING FROM THE PERMIT |
| | PACKAGE AND ARE REQUIRED FOR REVIEW. PLEASE PROVIDE: A) |
| | PERMIT APPLICATION B) ENERGY CALCULATIONS C) AC COOLING |
| | AND HEATING LOAD CALCULATIONS D) AHRI CERTIFICATE FOR |
| | THE AC SYSTEM. |
| | 2) SHEET A-6: THE MEP ENGINEER OF RECORD WHOSE TITLE |
| | BLOCK APPEARS ON THE PAGE SHALL SIGN AND SEAL THE PLAN |
| | IN COMPLIANCE WITH SECTION 61G15-23.002 FLORIDA |
| | ADMINISTRATIVE CODE, AND 471 FLORIDA STATUTES. ALL |
| | HANDWRIITEN NOTES ON THE PLAN SHALL BE SIGNED AND DATED |
| | BY THE ENGINEER OF RECORD. PLEASE NOTE THE SUBMITTED |
| | PLAN HAS BEEN REDLINED BY AN UNIDENTIFIED PERSON AND IS |
| | NO LONGER A VALID SUBMITTAL PER SECTION 107.2 WPB |
| | AMENDMENTS OT THE FBC-10 BUILDING CODE. PROVIDE A CLEAN |
| | SET OF DRAWINGS FOR REVIEW. |
| | 3) THE REVISED PLAN SHALL CLEARLY PROVIDE: A) AC |
| | EQUIPMENT SCHEDULE B) DUCT LAYOUT PLAN INCLUDING THE |
| | TYPE AND SIZE OF- SUPPLY AND RETURN DUCTS, TRANSFER |
| | DUCTS, DIFFUSER AND RETURN GRILLS, AND SUPPLY AND |
| | RETURN CFM'S ( SEE SECTION M1602.4 BALANCED RETURN AIR |
| | FOR TRANSFER DUCT SIZING). C) BATH, KITCHEN, AND DRYER |
| | EXHAUST SYSTEM DETAILS INCLUDING TYPES AND SIZES OF |
| | EXHAUST DUCTS, DUCT RUNS AND TERMINATION LOCATIONS, |
| | MAKE-UP AIR CALCULATIONS AND DETAILS FOR THE KITCHEN |
| | AND DRYER SYSTEMS. |
| | 4) SUBMIT SPECS FOR THE KITCHEN EXHAUST AND THE DRYER. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |