Plan Review Notes
Plan Review Notes For Permit 15061317
Permit Number 15061317
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-21 14:43:48NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PLANS NEED TO BE SIGNED AND SEALED AND WITH ORIGINAL
 SEAL AND SIGNATURE BY THE ENGINEERS SHOWN ON THE TITLE
 BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DRAWINGS FOR PUBLIC RECORDS. NOTE: THERE ARE
 TWO DIFFERENT PROFESSIONAL ENGINEERS ON THE TILE BLOCK
 OF DRAWINGS SUBMITTED. IT LOOKS LIKE THERE IS AN
 STRUCTURAL ENGINEER AND A MEP ENGINEER. DRAWINGS NEED
 TO BE SIGNED AND SEALED BY THE ENGINEER RESPONSIBLE FOR
 EACH DESIGN.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION IS BASED ON ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $276,948. THE
 PERMIT FEE BALANCE IS $5460.75.
  
 4- SHEET A-1:
 A) REVISE THE DESIGN DATA SHOWN ON THE FOOTING NOTES.
 THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE
 "B". SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. AND
 REVISE ALL THE DESIGN PRESSURES ON SHEET A-5
 ACCORDINGLY.
  
 B) REVISE THE PROJECT INFORMATION & DESIGN CRITERIA.
 THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE
 "C". SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. AND
 REVISE ALL THE DESIGN PRESSURES ACCORDINGLY.
  
 C) PROJECT INFORMATION & DESIGN CRITERIA: SPECIFY THE
 ULTIMATE WIND LOAD AND THE NOMINAL WIND LOAD. SEC.
 R301.2.1.3.
  
 D) CLEARLY SPECIFY THE ATTIC LIVE LOAD ON THE PROJECT
 INFORMATION & DESIGN CRITERIA. SEE FOOTNOTES "B" AND
 "G" OF TABLE R301.5 AND REVISE DESIGN CRITERIA AS
 REQUIRED.
  
 5- DRAINAGE PLAN SHOWN ON SHEET A-2. IT DOESN'T PROVIDE
 ANY INFORMATION SHOWING HOW THE SURFACE DRAINAGE IS
 DIVERTED TO A STORM SEWER OR ANY OTHER APPROVED POINT
 OF COLLECTION. NOTE: WATER NEEDS TO BE DIVERTED AWAY
 FROM FOUNDATION WALLS. SEE SEC. R401.3 AND REVISE PLAN
 AS REQUIRED.
  
 6- TYPICAL WALL SECTION ON SHEET A-2:
 A) THERE ARE TWO DIFFERENT NAIL TYPES AND SPACING SPECS
 FOR THE ROOF SHEATHING FASTENING. REVISE AS REQUIRED.
 SEE SEC. R803.2.3.1.
 NOTE: ALSO, COORDINATE WITH ROOF SHEATHING
 SPECIFICATIONS SHOWN THE "ROOF SHEATHING DETAIL" AND "
 FLOOR & ROOF SHEATHING FASTENER DETAIL" ON SHEET A-4.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WALL INSULATION SPECIFIED ON THIS TYP. WALL SECTION (RV
 PLUS SHIELD R-7). SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 NOTE: IS THERE ANY REASON WHY PROVIDING A HIGHER THAN
 STANDARD R INSULATION VALUE ON THE CONCRETE BLOCK
 WALL?.
 PLEASE COORDINATE INFORMATION ON THE ENERGY
 CALCULATIONS AND PLANS TO AVOID UNNECESSARY CONFLICTS
 OR DELAYS.
  
 C) PROVIDE SPECS FOR WALL FINISH. "TO MATCH EXIST.
 FINISH" DOESN'T APPLY. THERE IS NOT EXISTING FINISH.
 THIS IS A NEW HOUSE. SEC. R701.
  
 7- SHEET A-3:
 A) FLOOR PLAN IS NOT LEGIBLE. IT'S TOO DARK LETTERING
 AND NUMBERS ARE HARD TO READ. PLAN IS NOT CLEAR FOR
 SCANNING AND FILING PURPOSES. REVISE AS REQUIRED. SEC.
 107.2.1.4 CITY AMENDMENTS.
  
 B) SIZE OF ATTIC ACCESS SHOWN BY THE LAUNDRY AREA
 DOESN'T COMPLY WITH SEC. R807. REVISE AS REQUIRED.
  
 C) PROVIDE A BATHROOM WITH A DOOR SIZE THAT COMPLIES
 WITH SEC. R320.1.1.
  
 D) ENGINEER OF RECORD TO SPECIFY ANCHOR FASTENING
 SPACING OF THE GARAGE DOOR STRUCTURAL BUCK. IT'S NOT
 THE MANUFACTURER'S SPECIFICATIONS. SEC. R301.
  
 8- ROOF FRAMING PLAN ON SHEET A-4: PROVIDE COMPLETE
 ROOF FRAMING PLAN. SPECIFY ALL BEAMS AND LINTELS.
 SPECIFY ALL ROOF FRAMING MEMBERS AND CONNECTORS. SEC.
 R301.
  
 9- SHEET A-5: CODE ANALYSIS INFORMATION SHOWN ON TOP OF
 THE SHEET IS INCORRECT. SEC. 107.2.1 CITY AMENDMENTS.
 REVISE AS REQUIRED.
  
 10- SHEET A-5:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 SCREENED PORCH SHOWING COMPLIANCE WITH SEC. R301.
  
 11- SPECIFY CARBON MONOXIDE ALARM BY ALL THE BEDROOMS
 AS REQUIRED BY SEC. R315.
  
 12- ENERGY CALCULATIONS SUBMITTED:
 A) CONDITIONED AREA DOESN'T MATCH PLANS . REVISE AS
 REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) COORDINATE TYPE OF DOORS WITH PLANS AND PRODUCT
 APPROVALS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.0002(33) FOR:
 A) GARAGE DOORS THAT MEETS THE DESIGN PRESSURES FOR
 EXPOSURE "D" AS REQUIRED BY ITEM #4 ABOVE.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 IDENTIFY WINDOW MULLION SIZE TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES REQUIRED BY ITEM #4 ABOVE.
  
 C) FIXED WINDOWS AS SHOWN ON PLANS.
  
 D) GARAGE SIDE DOOR AS SHOWN ON PLANS.
  
 E) PRECAST LINTELS AS SHOWN ON PLANS.
  
 F) ALL TRUSS STRUCTURAL CONNECTORS SPECIFIED ON PLANS..
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NEXT TO THE SPECIFIED CONNECTOR.
  
 G) ENTRY DOORS AS SHOWN ON PLANS.
  
 14- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 **** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE REMOVE ANY REVISED SHEET. SUBMIT OLD COPIES
 FOR REFERENCE. DON"T STAPLE OLD COPIES TO NEW REVISED
 SET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]