| 2016-02-20 05:34:23 | 1) THE RESPONSE NARRATIVE STATES THAT THE 12TH FLOOR |
| | HAS BEEN REMOVED FROM THE SCOPE OF WORK BUT THERE ARE |
| | STILL PLANS FOR THE 12TH FLOOR BUILDOUT INCLUDED IN |
| | THIS SUBMITTAL. CLARIFY. |
| | 2) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE |
| | GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO |
| | THE TOP OF THE GRIPPING SURFACE PER THE 2010 |
| | FBC-ACCESSIBILITY SEC. 609.4. |
| | 3) SUBMIT THE OCCUPANT LOAD FOR THE 11TH LEVEL IN |
| | ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1. |
| | 4) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY |
| | WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH |
| | 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL |
| | APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL |
| | BE CENTERED ON THE APPLIANCE. |
| | 5) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER |
| | ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY |
| | SECS.212.1, 606. |
| | 6) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE |
| | CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER |
| | CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE |
| | MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86 |
| | INCHES ALLOWS FOR TOLERANCES. |
| | 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS & |
| | TOILET COMPARTMENTSL ON SHT.012 A1.03. COMPLY WITH 2010 |
| | FBC-ACCESSIBILITY & PLUMBING VOLUMES. |
| | 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET |
| | COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY |
| | WITH SEC.604.8.1. |
| | 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL |
| | COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4. |
| | 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH FLOOR |
| | SPACE PER 2010 FL. PLUMBING CODE. A MINIMUM OF 2 |
| | DRINKING FOUNTAINS ARE REQD. PER SEC. 211.2 OF THE 2010 |
| | FAC. |
| | 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010 |
| | FBC-ACCESSIBILITY SEC.603.2.3. |
| | 12) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC |
| | SEC.708.3.4. |
| | |