| Plan Review Notes For Permit 15061278 |
| Permit Number |
15061278 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-25 15:52:45 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15061278 | | | 2/25/16 | | | | | | 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS | | | FOR THE NEW AHU/CU 11-20. | | | 2) SHEET M4.01: THE VENTILATION CALCULATIONS FOR THE | | | LAUNDRY ROOMS IS NOT IN COMPLIANCE WITH TABLE 403.3. | | | PLEASE REVIEW THE TABLE AND REVISE THE CALCULATIONS | | | ACCORDINGLY. | | | 3) THE RESPONSE NARRATIVE FROM RGD CONSUILTING | | | ENGINEERS IS INDICATING THAT THE SCOPE OF WORK FOR THE | | | 12TH FLOOR "HAS BEEN REMOVED FROM THE PROJECT", HOWEVER | | | THE 12TH FLOOR PLAN SHEETS ARE STILL INCLUDED IN THE | | | PLAN SETS. PLEASE CONTACT PLAN REVIEW LIBRARIAN | | | CAROLINE PUELL OR LAURA MARCHANT AND HAVE ALL 12TH | | | FLOOR PLAN SHEETS REMOVED. | | | 4) M2.02: THE EXHAUST GRILL IN THE WOMEN'S TOILET ROOM | | | IS MISLABELED AS A SUPPLY DIFFUSER. | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS | | | WITH AN APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD. | | | 6) SUBMIT TWO COPIES OF THE NOA FOR THE ROOF STAND WITH | | | AN APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|