| Date |
Text |
| 2015-07-25 09:44:02 | 1) SHT.005-A0.4 - MOUNTING HEIGHTS- THE HEIGHT OF THE |
| | GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR TO |
| | THE TOP OF THE GRIPPING SURFACE PER THE 2010 |
| | FBC-ACCESSIBILITY SEC. 609.4. |
| | 2) SUBMIT THE OCCUPANT LOAD FOR EACH LEVEL IN |
| | ACCCORDANCE WITH 2010 FBC-BUILDING, TABLE 1004.1.1. |
| | 3) WASHING MACHINES AND CLOTHES DRYERS SHALL COMPLY |
| | WITH THE 2010 FBC-ACCESSIBILITY, SECS.611.1 THROUGH |
| | 611.4. A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL |
| | APPROACH SHALL BE PROVIDED. THE CLEAR FLOOR SPACE SHALL |
| | BE CENTERED ON THE APPLIANCE. |
| | 4) BREAK ROOM SINKS AND SINKS IN THE BUSINESS CENTER |
| | ROOMS SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY |
| | SECS.212.1, 606. |
| | 5) SUBMIT ENLARGED TOILET ROOM PLANS SHOWING THE INSIDE |
| | CLEAR DIMENSIONS OF THE TOILET ROOMS. IF THE WATER |
| | CLOSET AND LAVATORY ARE LOCATED ON THE SAME WALL THE |
| | MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT PERFECT. 86 |
| | INCHES ALLOWS FOR TOLERANCES. |
| | 6) SHT.012A1.04 - ROOMS 1212 & 1213 - A CLEARANCE OF 36 |
| | INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM MEASURED |
| | FROM THE CONTROL WALL SHALL BE PROVIDED PARALLEL TO THE |
| | SHOWER ENTRANCES PER THE 2010 FBC-ACCESSIBILITY, |
| | SEC.608.2.1. THE PLANS DO NOT SHOW THE CLEARANCE. |
| | 7) SHOW THE INSIDE CLEAR DIMENSIONS OF THE SHOWERS, |
| | TOILET COMPARTMENTS, & URINAL STALL ON SHT.012 A1.04. |
| | COMPLY WITH 2010 FBC-ACCESSIBILITY & PLUMBING VOLUMES. |
| | 8) 2010 FBC -ACCESSIBILITY SEC.213.3.1 - WHERE TOILET |
| | COMPARTMENTS ARE PROVIDED, AT LEAST ONE SHALL COMPLY |
| | WITH SEC.604.8.1. |
| | 9) WHERE LAVATORIES ARE PROVIDED AT LEAST ONEE SHALL |
| | COMPLY W/FBC-ACCESSIBILITY SEC.606, 213.3.4. |
| | 10) DRINKING FOUNTAINS ARE REQUIRED IN THE 11TH AND |
| | 12TH FLOOR SPACES PER 2010 FL. PLUMBING CODE. A MINIMUM |
| | OF 2 DRINKING FOUNTAINS ARE REQD. ON EACH FLOOR PER |
| | SEC. 211.2 OF THE 2010 FAC. |
| | 11) TOILET ROOM #1152 - THE DOOR SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2010 |
| | FBC-ACCESSIBILITY SEC.603.2.3. |
| | 12) SHTS.070 P5.11 & 071 P5.12 - THE STACKS FOR THE |
| | WASHING MACHINES SHALL BE A MINIMUM OF 3" PER THE 2010 |
| | FPC SEC.406.3. |
| | 13) BRANCH VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH |
| | SHALL BE INCREASED ONE PIPE SIZE FOR THE ENTIRE |
| | DEVELOPED LENGTH OF THE VENT PIPE PER 2010 FPC |
| | SEC.916.4.1.(SEE VENTS FOR TOILET ROOMS IN LOCKERS ON |
| | LEVEL 12). |
| | 14) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC |
| | SEC.708.3.4. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |