| 2015-07-14 14:33:52 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15061278 |
| | 7/14/15 |
| | |
| | 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR |
| | THE NEW AHU/CU 11-20 SYSTEM IN ACCORDANCE WITH ACCA |
| | MANUAL N OR THE ACCA/ASHRAE STANDARD 183- REFERENCE |
| | SECTION 503.2.1 FBC-10 ENERGY CONSERVATION. |
| | 2) IN ACCORDANCE WITH SECTION 709.1 FBC-10 EXISTING |
| | BUILDING, PROVIDE MINIMUM VENTILATION CALCULATIONS FOR |
| | THE RECONGFIGURED ROOMS AND SPACES ON THE 11TH AND 12TH |
| | FLOORS- REFERENCE TABLE 403.3 FBC-10 MECHANICAL. |
| | PROVIDE A SCHEDULE ON THE PLAN INDICATING THE MINIMUM |
| | REQUIRED CFM'S OF O/A OR EXHAUST, AND THE CFM'S |
| | PROVIDED. REFERENCE SECTIONS 503.4.5.1 AND 503.4.5.2 |
| | FBC-10 ENERGY CONSERVATION, AND ADD NOTES ON SHEET M6.1 |
| | TO INDICATE VAV TERMINAL DEVICE COMPLIANCES REGARDING |
| | O/A. |
| | 3) NEW FIRE DAMPERS ARE SHOWN ON THE PLANS: PROVIDE AN |
| | EQUIPMENT SCHEDULE ON THE PLAN LISTING THE MAKES AND |
| | MODELS, FIRE-RESISTANCE RATINGS, AND HOW THEY WILL BE |
| | ACTUATED- PROVIDE A SEQUENCE OF OPERATION, AND CLARIFY |
| | IF ANY OTHER ALTERATIONS TO THE SMOKE CONTROL SYSTEM |
| | ARE PROPOSED. |
| | 4) THE 12TH FLOOR PLAN LAYOUT ON THE ARCHITECTURAL |
| | DEMOLITION SHEET (A1.02) DOES NOT MATCH THE LAYOUT |
| | SHOWN ON THE MECHANICAL DEMO SHEET (M2.0). |
| | 5) SHEET M2.02: EXHAUST VENTILATION FOR THE TOILET |
| | ROOMS IS REQUIRED. PLEASE PROVIDE THE DETAILS, EXHAUST |
| | DUCT RUNS, AND EXHAUST FAN SCHEDULES ON THE PLANS- |
| | TABLE 403.3 FBC-10 MECHANICAL. |
| | 6) M2.04: EXHAUST VENTILATION FOR THE LOCKER/TOILET |
| | ROOMS IS REQUIRED. PROVIDE THE DETAILS, DUCT RUNS, AND |
| | FAN SCHEDULES ON THE PLAN. |
| | 7) M2.02 & M2.04 PROVIDE MAKE-UP AIR FOR THE DRYERS- |
| | REFERENCE SECTION 504.5 FBC-10 MECHANICAL. NOTE THERE |
| | IS A DUCT DROP SHOWN AT THE FRONT OF THE 12TH FLOOR |
| | DRYER CLOSET, HOWEVER DOOR 1117 ENCLOSING THE CLOSET IS |
| | NOT LISTED AS A LOUVERED DOOR ON THE SCHEDULE ON SHEET |
| | A6.01. PROVIDE THE TOTAL LENGTHS OF THE DRYER EXHAUST |
| | DUCT RUNS IN COMPLIANCE WITH SECTION 504.6.4, AND |
| | SUBMIT PRODUCT DATA CUTSHEETS FOR THE APPLIANCES. |
| | 8) M5.02: THE DESIGN PROFESSIONAL OF RECORD SHALL |
| | CERTIFY THAT THE CU WILL BE INSTALLED TO WITHSTAND 170 |
| | MPH WIND LOADS AND PRESSURES- REFERENCE 301.12 FBC-10 |
| | MECHANICAL. PROVIDE NOTES ON THE PLAN INDICATING |
| | COMPLIANCE. |
| | |