| Notes |
| Date |
Text |
| 2015-07-06 20:28:13 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER WAS UNABLE TO COMPLETE THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE CORRECTIONS NOTED. | | | | | | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | | RESUBMITTED FOR A SECOND REVIEW: | | | | | | 1. SEPARATE PERMIT REQUIRED FOR FIRE ALARM | | | INSTALLATION. THEREFORE DO NOT INCLUDE THE FIRE ALARM | | | DEVICES ON THIS SHEET. | | | 2. THESE PAGES ARE TOO CLUTTERED TO PROPERLY IDENTIFY | | | THE DIFFERENT ROOMS. PROVIDE A SEPARATE SHEET FOR THE | | | REFLECTED CEILING. | | | 3. EMERGENCY STAIRS NEED TO BE IDENTIFIED TO ASCERTAIN | | | PROPER LOCATION OF EXIT LIGHTING. | | | 4. EMERGENCY LIGHTING IS NOT CLEARLY INDICATED | | | ACCORDING TO THE LEGEND. | | | 5. IN THE 12TH FLR. INDICATE THE AREA DIRECTLY ADJACENT | | | TO YOUR SCOPE OF WORK WITH RESPECT TO THE EXITS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|