| 2015-08-26 13:41:25 | THIS REVIEW WAS STARTED ON 7/17/15. ON 8/4/15 I WENT |
| | BACK TO IT AND TODAY 8/26/15 I COMPLETED THE REVIEW. |
| | THE APPLICATION/REVIEW FAILED ELECTRICAL AS NOTED |
| | BELOW: |
| | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | PAGE FA2.1.1 |
| | 1. THIS SHEET IS MISSING THE COMPLETE TITLE BLOCK |
| | 2. THIS SHEET HAS NO F/A MARKINGS. |
| | |
| | PAGE FA2.1.2 |
| | 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 2. SAME AS CHANGE MARK 1 FOR VARIOUS LOCATIONS ON THIS |
| | PAGE. |
| | 3. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL |
| | STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A |
| | PULL BOX UNDER 200FT. |
| | 4. IDENTIFY/INCLUDE THE ?DD INSIDE THE SQUARE? SYMBOL |
| | ON YOUR LEGEND. DUCT DETECTOR? |
| | |
| | PAGE FA2.1.3 THROUGH FA2.1.8 APPEAR TO HAVE SIMILAR |
| | ISSUES. BASICALLY NO MANUAL INITIATION DEVICES APPEAR |
| | ON THE FLOOR PLANS. |
| | 1. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 2. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 3. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 4. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 5. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 6. PER NFPA 72, SECTION 17.14.8, ADDITIONAL PULL |
| | STATIONS SHALL BE PROVIDED TO KEEP TRAVEL DISTANCE TO A |
| | PULL BOX UNDER 200FT. |
| | 7. PER NFPA 72, SECTION 17.14.6, MANUAL PULL STATION |
| | REQUIRED WITHIN 5' OF EXIT. |
| | 8. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM. |
| | 9. SMOKE DETECTOR INSIDE ELECTRICAL EQUIPMENT ROOM. |
| | |
| | THERE APPEARS TO BE SMOKE BARRIER DOOR IN THE CORRIDORS |
| | W/O THE SMOKE DETECTORS AND OR DOOR HOLDER RELAYS. IF |
| | THE CORRIDORS ARE COMPARTMENTALIZED SHOW THE REQUIRED |
| | DEVICES. |
| | |
| | PAGES FA2.1.9 ROOF |
| | 1. THIS PAGE IS LACKING THE MANUAL INITIATION DEVICES |
| | AS WELL. |
| | 2. THERE ARE SYMBOLS NOT IDENTIFIED ON THE LEGEND. |
| | |
| | PAGES FA3.1.1.3.1.3 & FA3.1.1.3.1.5 RISER DIAGRAMS |
| | 1. NOTHING SHOWN FOR THE GROUND FLOOR ON THE RISER |
| | DIAGRAM APPEARS ON THE CORRESPONDING PAGE. |
| | 2. THE CONTINUATION OF THE RISER DIAGRAM, PROBABLY PAGE |
| | FA3.1.1.3.1.4 (THIRD TO FIFTH FLOORS) IS MISSING. |
| | 3. THE CONTINUATION OF THE RISER DIAGRAM FOR THE |
| | SEVENTH FLOOR TO ROOF IS ALSO MISSING. |
| | 4. THE ENTIRE RISER DIAGRAMS WILL HAVE TO BE RECREATED |
| | TO INCLUDE THE MISSING DEVICES ONCE ADDED TO PLANS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |
| 2015-08-04 16:37:32 | REVIEW RESULTS PENDING RESPONSE FROM WES. |