| 2015-11-17 21:15:15 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. PLEASE NOTE THAT THE USE OF A CO DETECTOR IS NOT A |
| | VIOLATION. THOUGH IT IS NOT A REQUIREMENT BECAUSE THERE |
| | ARE NO ATTACHED GARAGES OR GAS APPLIANCES, THE EXTRA |
| | PROTECTION IS WELL WORTH THE EFFORT. |
| | 2. PREVIOUSLY YOU REFERRED TO ?ROMEX? NOW YOU REFER TO |
| | ?BX? PLEASE NOTE THAT THESE ARE NOT APPROVED WIRING |
| | METHODS. THE CODE DOES NOT RECOGNIZE ROMEX OR BX. |
| | CORRECT YOUR NOTE ACCORDINGLY. |
| | 3. INDICATE HOW THE REAR STAIRS ARE BEING ILLUMINATED |
| | AND SWITCHED. A WALL SCONCE ON THE EXTERIOR DOOR IS NOT |
| | SUFFICIENT TO ILLUMINATE THE COMPLETE STAIRWAY. |
| | FURTHERMORE, SHOW THE AUTOMATIC/REMOTE SWITCHING. |
| | 4. CORRECT THE WET LOCATION NOTES AS THE QUOTED CODE |
| | SECTION EITHER DO NOT EXIST OR ARE INAPPLICABLE. |
| | 5. NEC REQUIRES A LIGHT ON THE OUTSIDE OF THE FRONT |
| | DOOR OF THE BLDG. |
| | 6. ALL PANELS ARE LABELED ?C?, CORRECT ACCORDINGLY. |
| | 7. THE NOTES CALL FOR A 100 AMP HOUSE PANEL AND THE |
| | PLANS SHOW A 150 AMP PANEL WITH A CONNECTED LOAD OF 150 |
| | AMP. CORRECT ACCORDINGLY. |
| | 8. PROVIDE LOAD CALCS AS REQUIRED BY NEC. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |