Plan Review Notes For Permit 15061267
Permit Number 15061267
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-22 04:32:441) THE PLANS SHOW THE WASHER/DRYERS ON A PORCH. IS THIS
 PORCH OPEN TO THE ELEMENTS? IF SO, SUBMIT APPLIANCE
 SPECIFICATIONS/INSTALLATION MANUAL THAT SHOWS THAT THEY
 CAN BE INSTALLED IN THIS TYPE OF ENVIRONMENT. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A SANITARY AND WATER RISER FOR THE ADDITION
 OF THE WASHING MACHINES.WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 3) THIS STRUCTURE DOES NOT FALL UNDER THE RESIDENTIAL
 BUILDING CODE SO THE WASHING MACINE STANDPIPE SHALL
 CONNECT TO A 3" STACK PER THE 2010 FBC-PLUMBING,
 SEC.406.3.
 4) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE TANKLESS
 WATER HEATERS TO BE INSTALLED.THEY ARE ALSO SHOWN AS
 BEING LOCATED ON THE PORCH. IF THE PORCH IS OPEN TO THE
 ELEMENTS, SUBMIT DOCUMENTATION FROM THE MANUFACTURER
 THAT THE UNIT CAN BE INSTALLED EXPOSED TO THE ELEMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  