| Plan Review Notes For Permit 15061267 |
| Permit Number |
15061267 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-30 15:52:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE STAIR AND RAILING DETAIL FOR BOTH STAIRS. | | | EXISTING STAIRS SHALL COMPLY WITH NFPA 101, CHAPTER 31, | | | CHAPTER 7, 7.2.2.2.1.1 (2). | | | | | | 2. THERE APPEARS TO BE CLOSETS UNDER THE LANDING OF THE | | | EXIT STAIR. | | | | | | 7.2.2.5.3 USABLE SPACE | | | | | | ENCLOSED, USABLE SPACE SHALL BE PERMITTED UNDER STAIRS, | | | PROVIDED THAT ALL OF THE FOLLOWING CRITIERIA ARE MET: | | | | | | (1) THE SPACE SHALL BE SEPARATED FROM THE ENCLOSURE BY | | | THE SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE. | | | | | | (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE | | | FROM WITHIN THE STAIR ENCLOSURE. | | | | | | (3) THE SPACE IS NOT USED FOR STORAGE OF FLAMMABLE, OR | | | OTHERWISE HAZARDOUS MATERIALS. | | | | | | 3. FOR THE DOORS WITHIN THE EXIT STAIRWAY AND EXIT PATH | | | (2ND FL) PROVIDE A DOOR SCHEDULE INCLUDING HARDWARE | | | MEETING THE REQUIREMENTSOF NFPA 31, 31.2.2.1.2 | | | |
|