Plan Review Notes
Plan Review Notes For Permit 15061267
Permit Number 15061267
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-30 15:52:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE STAIR AND RAILING DETAIL FOR BOTH STAIRS.
 EXISTING STAIRS SHALL COMPLY WITH NFPA 101, CHAPTER 31,
 CHAPTER 7, 7.2.2.2.1.1 (2).
  
 2. THERE APPEARS TO BE CLOSETS UNDER THE LANDING OF THE
 EXIT STAIR.
  
 7.2.2.5.3 USABLE SPACE
  
 ENCLOSED, USABLE SPACE SHALL BE PERMITTED UNDER STAIRS,
 PROVIDED THAT ALL OF THE FOLLOWING CRITIERIA ARE MET:
  
 (1) THE SPACE SHALL BE SEPARATED FROM THE ENCLOSURE BY
 THE SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE.
  
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE.
  
 (3) THE SPACE IS NOT USED FOR STORAGE OF FLAMMABLE, OR
 OTHERWISE HAZARDOUS MATERIALS.
  
 3. FOR THE DOORS WITHIN THE EXIT STAIRWAY AND EXIT PATH
 (2ND FL) PROVIDE A DOOR SCHEDULE INCLUDING HARDWARE
 MEETING THE REQUIREMENTSOF NFPA 31, 31.2.2.1.2
  