| 2015-07-23 17:20:55 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | |
| | 1. ROMEX, AS MENTIONED IN YOUR NOTES IS INTENDED AS A |
| | CABLE TYPE, ROMEX IS A BRAND NAME AND NOT A TYPE OF |
| | LISTED CABLE; USE OF NM, NMC OR NMS ETC. |
| | 2. YOU SHALL PROVIDE SMOKE DETECTORS AS PER FBC-R 314. |
| | 3. DISCONNECTS FOR AHU SHALL BE MADE ACCESSIBLE. |
| | 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| | LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| | REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| | 50 LB. |
| | 5. REAR STAIRS SHALL HAVE THE REQUIRED ILLUMINATION AND |
| | BE SWITCHED FROM BOTH THE TOP AND BOTTOM OF STAIRS. |
| | 6. PROVIDE A HOUSE METER & PANEL FOR COMMON LOADS SUCH |
| | AS HOUSE LIGHTING (CORRIDORS AND STAIRS, EMERGENCY |
| | LIGHTING AND SERVICE OUTLETS FOR CONDENSING UNITS.) |
| | 7. CORRECT RISER DIAGRAM TO CONFIRM MAIN SERVICE |
| | DISCONNECTS ARE GROUPED TOGETHER AND NEXT TO THE |
| | ELECTRIC SERVICE METERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |