Plan Review Notes
Plan Review Notes For Permit 15061267
Permit Number 15061267
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-20 12:53:28SHILL'S DESK
2015-07-23 17:20:55PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. ROMEX, AS MENTIONED IN YOUR NOTES IS INTENDED AS A
 CABLE TYPE, ROMEX IS A BRAND NAME AND NOT A TYPE OF
 LISTED CABLE; USE OF NM, NMC OR NMS ETC.
 2. YOU SHALL PROVIDE SMOKE DETECTORS AS PER FBC-R 314.
 3. DISCONNECTS FOR AHU SHALL BE MADE ACCESSIBLE.
 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB.
 5. REAR STAIRS SHALL HAVE THE REQUIRED ILLUMINATION AND
 BE SWITCHED FROM BOTH THE TOP AND BOTTOM OF STAIRS.
 6. PROVIDE A HOUSE METER & PANEL FOR COMMON LOADS SUCH
 AS HOUSE LIGHTING (CORRIDORS AND STAIRS, EMERGENCY
 LIGHTING AND SERVICE OUTLETS FOR CONDENSING UNITS.)
 7. CORRECT RISER DIAGRAM TO CONFIRM MAIN SERVICE
 DISCONNECTS ARE GROUPED TOGETHER AND NEXT TO THE
 ELECTRIC SERVICE METERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  