| 2015-07-07 14:59:45 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15061246 |
| | ADD: 1100 W. TECHNOLOGY PLACE |
| | CONT: MGM EQUIPMENT |
| | TEL: (954)963-3995 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 07/2015 |
| | ACTION: DENIED |
| | |
| | 1) DOCUMENTS SUBMITTED, SUPPORT STUCTURE FOR MECHANICAL |
| | EQUIPMENT FROM MWS ENGINEERING NOTE # 20 PROVIDES THE |
| | WIND DESIGN ; |
| | 155 MPH VULT PLEASE CORRECT TO 170 VULT |
| | BUILDING RISK CATEGORY I PLEASE CORRECT TO: BUILD. RISK |
| | CATEGORY II |
| | EXPOSURE D PLEASE CORRECT TO EXPOSURE C |
| | ROOFTOP STRUCTURE. COMPLY WITH 1609.8 ROOFTOP |
| | STRUCTURES AND EQUIPMENT. |
| | |
| | 2) THE SAME ROOF STAND PLEASE BE ADVISED TO TAKE YOUR |
| | VERTICAL MEASUREMENT FOR COMPLIANCE WITH 2010 FBC-B |
| | TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED |
| | MECHANICAL EQUIPMENT, THE VERTICAL MEASUREMENT IS TAKEN |
| | FROM THE LOWEST (BOTTOM) OF THE HORIZONTAL FRAMING |
| | MEMBER. SEE TABLE MINIMUM CLEAR REQUIRED HEIGHT TO THE |
| | BOTTOM OF THE LOWEST HORIZONTAL FRAMING MEMBER IS 30 |
| | INCHES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |