| 2015-07-07 17:22:40 | NEC 680.62(A)(1) ADDRESSES LISTED UNITS, AS I WAS | | | UNABLE TO FIND A "UL" LISTING ON ANY OF THE COMPONENTS | | | OR THE UNIT AS A WHOLE. THEREFORE THE PROPOSED OUTLET | | | SHALL BE GFCI PROTECTED. ALL METAL COMPONENTS OF THIS | | | SYSTEM OR WITHIN 5' OF THE WATER'S EDGE SHALL BE | | | CONNECTED TO THE EQUIPMENT GROUNDING CONDUCTOR AS | | | DESCRIBED IN 680.62(D). SEE NEC 680 PART VI FOR | | | ADDITIONAL REQUIREMENTS. |
|