| 2015-07-14 12:08:50 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2010 |
| | |
| | 1ST REVIEW: TEST REPORTS FOR QUIETWALK UNDERLAYMENT, |
| | LAMINATE FLOORING WERE SUBMITTED |
| | 2ND REVIEW: SPEC SHEETS FOR QUIETWALK SUBMITTED |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. FBC 1207.2, THE ASSEMBLY TESTED USED AN 8" SLAB FOR |
| | THE STC TEST. PROVIDE THE SLAB THICKNESS FOR THIS |
| | PROJECT. IF THE SLAB IS NOT 8", ADDITIONAL INFORMATION |
| | WILL BE REQUIRED SUCH AS A TEST REPORT WHICH USES AN 6" |
| | SLAB (LIKE THE IIC TEST), A DESIGN PROFESSIONAL'S |
| | COMPARATIVE ANALYSIS, OR THE MANUFACTURER'S ANALYSIS |
| | (ON LETTERHEAD). |
| | |
| | 2ND REVIEW, THIS WAS NOT PROVIDED. MORE SPEC SHEETS |
| | WERE PROVIDED. SLAB THICKNESS FOR THIS JOB NOT |
| | PROVIDED, ANALYSIS (OR TEST USING A 7" OR 6" SLAB) NOT |
| | PROVIDED. |
| | |
| | 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | |
| | 3. TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| | FOR PERMIT ISSUANCE, FBC 107. |
| | |
| | NEW COMMENT: |
| | |
| | 4. SPEC SHEETS ARE NOT ACCEPTABLE IN LIEU OF TEST |
| | REPORTS DUE TO GENERAL DISCREPANCIES. |
| | |
| | |
| | |
| | |