| Plan Review Notes For Permit 15061222 |
| Permit Number |
15061222 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-06 10:10:31 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | TEST REPORTS FOR QUIETWALK UNDERLAYMENT, LAMINATE | | | FLOORING WERE SUBMITTED | | | | | | 1. FBC 1207.2, THE ASSEMBLY TESTED USED AN 8" SLAB FOR | | | THE STC TEST. PROVIDE THE SLAB THICKNESS FOR THIS | | | PROJECT. IF THE SLAB IS NOT 8", ADDITIONAL INFORMATION | | | WILL BE REQUIRED SUCH AS A TEST REPORT WHICH USES AN 6" | | | SLAB (LIKE THE IIC TEST), A DESIGN PROFESSIONAL'S | | | COMPARATIVE ANALYSIS, OR THE MANUFACTURER'S ANALYSIS | | | (ON LETTERHEAD). | | | | | | 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | | E 84 OR UL 723. | | | | | | 3. TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | FOR PERMIT ISSUANCE, FBC 107. | | | | | | |
|