| 2016-08-18 19:17:44 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| | EXHAUST SYSTEMS. |
| | |
| | (1) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1. |
| | (2) PROVIDE EQUIPMENT INFORMATION ON EXHAUST FAN IN |
| | BATHROOM. |
| | (3) PROVIDE TIE DOWN DETAIL ON PLANS OR MANUFACTURER |
| | DATA INFORMATION FOR THE SPECIFIC TIE DOWN DEVICES |
| | BEING USED. |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |
| | (4) PROVIDE AHRI |
| | |
| | JORGE VALIDO |
| | WPB MECHANICAL INSPECTOR/PLANS EXAMINER |