2015-11-19 10:33:501ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6700
 [email protected]
  
  
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 NEC 220.82 A AMPACITY OF 100 AMPS OR GREATER/ COULD
 ONLY FILL BREAKER 80 % OF LOAD
 PROVIDE GROUNTING ELECTRODE IN ATTACHED BUILDING PER
 NEC 250
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  