| Plan Review Notes For Permit 15061210 |
| Permit Number |
15061210 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-19 10:33:50 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6700 | | | [email protected] | | | | | | | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | NEC 220.82 A AMPACITY OF 100 AMPS OR GREATER/ COULD | | | ONLY FILL BREAKER 80 % OF LOAD | | | PROVIDE GROUNTING ELECTRODE IN ATTACHED BUILDING PER | | | NEC 250 | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | |
|