Plan Review Notes
Plan Review Notes For Permit 15061210
Permit Number 15061210
Review Stop R
Sequence Number 1
Notes
Date Text
2015-08-19 08:25:441ST REVIEW: FBC 2010
  
 FBC 107 - FURTHER SPECIFY THE ROOFING SYSTEM TO BE USED
 FOR THE FLAT ROOF . DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS OF FBCR 905.9 EG: PROVIDE TIN TAG SPACING
 FOR 30# UNDERLAYMENT INCLUDING ENHANCED FASTENING FOR
 ZONES 2 & 3, NUMBER OF PLYS AND MATERIAL AND
 APPLICATION. SHOW THE ROOF DRAINAGE METHOD.
 ALTERNATIVELY, PROVIDE ROOF COVERING PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD, INCLUDE THE SYSTEM FOR TNE TYPE "S" TILE ROOF
 OVERHANG..
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  