| Plan Review Notes For Permit 15061210 |
| Permit Number |
15061210 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-19 10:29:02 | 1ST REVIEW: FBC 2010 | | | | | | REVISE PLAN TO INDICATE COMPLIANCE WITH THE FOLLOWING: | | | | | | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET | | | | | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | | | | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | | 25? OF MECHANICAL EQUIPMENT | | | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | | | FBC 1006.1.1 PER FBC-R, T-E3403 | | | ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN | | | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND | | | STRUCTURE, BEDROOM EXIT.. | | | | | | ADDITIONALLY, NO CIRCUIT OR DICCONNECT IS SHOWN FOR THE | | | A/C EQUIPMET OR THE WATER HEATER, THE LOAD CALCULATION | | | DOES NOT ACCOUNT FOR THESE LOADS. | | | | | | INDICATE THE LOCATION OF THE SERVICE. IS THE 60AMP | | | PANEL FOR THE ACCESSORY STRUCTURE FED FROM THE SERVICE | | | TO THE HOUSE OR IS THERE TO BE A SEPARATE SERVICE. IS | | | THIS AN ACCESSORY BUILDING OR A SEPARATE DWELLING UNIT? | | | PROVIDE AN ACCURATE SERVICE RISER DIAGRAM,. ACCURATE | | | LOAD CALCULATIONS, AND PANEL SCHEDULES. | | | | | | NOTE, A COMPLETE REVIEW CANNOT BE PERFORMED DUE TO THE | | | LACK OF INFORMATION PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|