| Plan Review Notes For Permit 15061203 |
| Permit Number |
15061203 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-15 05:17:13 | 1) SHT. P-2 - THE WATER CLOSET, SHOWER AND TUB IN THE | | | MASTER BATH ARE NOT PROPERLY VENTED AS DRAWN. FBC- | | | RESIDENTIAL SEC.P3101.2, P3101.2.1. | | | 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON | | | THE FLOOR PLAN.THE PLANS SHOW A TANK TYPE WATER HEATER | | | IN THE GARAGE. WHAT IS BEING INSTALLED, A TANKLESS | | | WATER HEATER OR A TANK TYPE? CLARIFY.WPB AMEND. TO FBC | | | SEC.107.2.1. | | | 3) IF THE TANK TYPE WATER HEATER IN THE GARAGE IS | | | REMAINING, IT SHALL BE PROTECTED FROM VEHICLE IMPACT | | | DAMAGE,SUBMIT DETAILS AS TO THE METHOD OF | | | PROTECTION.WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) THE GAS RISER SHOWS A GAS GRILL ON IT BUT IT IS NOT | | | SHOWN ANYWHERE ON THE PLANS. CLARIFY. | | | 5) SHOW THE LOCATION OF THE GAS METER ON THE PLANS. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 6) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE | | | PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS | | | APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS | | | APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND | | | COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS | | | REQUIRED BY THE CODE. | | | 7) THE PLANS REFER TO PLUMBING AT THE SUMMER KITCHEN | | | BUT NO PLUMBING IS SHOWN ON THE FLOOR PLAN OR THE | | | SANITARY RISER.CLARIFY. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|