2015-07-15 05:17:131) SHT. P-2 - THE WATER CLOSET, SHOWER AND TUB IN THE
 MASTER BATH ARE NOT PROPERLY VENTED AS DRAWN. FBC-
 RESIDENTIAL SEC.P3101.2, P3101.2.1.
 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE FLOOR PLAN.THE PLANS SHOW A TANK TYPE WATER HEATER
 IN THE GARAGE. WHAT IS BEING INSTALLED, A TANKLESS
 WATER HEATER OR A TANK TYPE? CLARIFY.WPB AMEND. TO FBC
 SEC.107.2.1.
 3) IF THE TANK TYPE WATER HEATER IN THE GARAGE IS
 REMAINING, IT SHALL BE PROTECTED FROM VEHICLE IMPACT
 DAMAGE,SUBMIT DETAILS AS TO THE METHOD OF
 PROTECTION.WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE GAS RISER SHOWS A GAS GRILL ON IT BUT IT IS NOT
 SHOWN ANYWHERE ON THE PLANS. CLARIFY.
 5) SHOW THE LOCATION OF THE GAS METER ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS
 APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS
 APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND
 COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS
 REQUIRED BY THE CODE.
 7) THE PLANS REFER TO PLUMBING AT THE SUMMER KITCHEN
 BUT NO PLUMBING IS SHOWN ON THE FLOOR PLAN OR THE
 SANITARY RISER.CLARIFY.
  
  