| Plan Review Notes For Permit 15061203 |
| Permit Number |
15061203 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-08-21 09:11:31 | MECHANICAL PROVISO: | | | 8/20/15 | | | | | | 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE KITCHEN EXHAUST HOOD SHALL BE | | | ON-SITE AT TIME OF INSPECTION. | | | REVISION REQUIRED FOR MAKEUP AIR IF APPLICABLE. | | | M1503.4 FBC-10 RESIDENTIAL- MAKEUP AIR REQUIRED. | | | EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF | | | 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED | | | WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE | | | EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE | | | EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE | | | AUTOMATICALLY CONTROLLED TO START AND OPERATE | | | SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. | | | |
|