Notes
Date Text
2015-08-21 09:11:31MECHANICAL PROVISO:
 8/20/15
  
 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE KITCHEN EXHAUST HOOD SHALL BE
 ON-SITE AT TIME OF INSPECTION.
 REVISION REQUIRED FOR MAKEUP AIR IF APPLICABLE.
 M1503.4 FBC-10 RESIDENTIAL- MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  